24 V DC supply (-TB7)
Insulation monitor (-BE1)
Local control panel (LCP).
RJ45 terminal blocks 1 and 2 (-RJ45_1 and RJ45_2)
Protection terminal block set (-XD11)
Socket outlet (-XD10)
Contactor control circuit terminal block (-XD0)
Cabinet heater terminal block (-XD4)
Customer terminal block/option C0 terminal block (-
XDW)
Thermal trip indicator relay, input power options
cabinet (-KFJ.1)
Thermal trip indicator relay, output lter cabinet (-
KFJ.2)
Thermal trip indicator relay, input lter cabinet (-
KFJ.3)
PHF capacitor connect/disconnect contactor relay (-
QAF)
+24 DC supply protection MCB (-FC7)
AC circuit protection MCB (-FC6)
AC distribution circuit terminal block (-XD1)
Auxiliary relay for heater (-QAM)
Contactor control circuit protection MCB (-FC10)
Cabinet light/socket outlet protection MCB (-FCC)
Cabinet heater(s) circuit protection MCB (-FCE)
DC distribution circuit terminal block (-XD3)
Motor heater circuit protection MCB (-FCN)
AC fan supply terminal block set (-XDY)
Option C2 terminal block set (-XDF)
Basic I/O terminal block and option A, B, D card ter-
minal block set (-XD2)
Door components terminal block set (-XDJ)
Grounding clamp for the shield termination of wires.
5.7.3 Control Terminals
Table 43: Serial Communication Terminals
XD2 ter-
minal
Parameter
Default
Setting
Description
1
Integrated RC-lter for cable shield. Used only for connecting the shield in
case of EMC problems.
2
Parameter group 8-3* FC
Port Settings
RS485 interface. A switch (BUS TER.) is provided on the control card for bus
termination resistance. See Illustration 5.22.
3
Parameter group 8-3* FC
Port Settings
Table 44: Digital Input/Output Terminal Descriptions
XD2 ter-
minal
Parameter
Default setting
Description
10, 11
+24 V DC
24 V DC supply voltage for digital inputs and external trans-
ducers. Maximum output current 200 mA for all 24 V loads.
12
Parameter 5-10 Terminal 18 Digital
Input
[8] Start
Digital inputs.
13
Parameter 5-11 Terminal 19 Digital
Input
[10] Reversing
16
Parameter 5-14 Terminal 32 Digital
Input
[0] No operation
AQ357954340588en-000201 / 130R088170 | Danfoss A/S © 2020.09
Electrical Installation
VLT® Refrigeration Drive FC 103
Operating Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 302 N110 and is the answer not in the manual?

Danfoss VLT FC 302 N110 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 302 N110
CategoryDC Drives
LanguageEnglish

Related product manuals