Control word according to Fieldbus Prole
To select Prodrive in the control word, parameter
512 Telegram Prole must be set to Prodrive [0].
The control word is used to send commands from a
master (e.g. a PC) to a slave (frequency converter).
Master
Slave.
Bit Bit = 0 Bit =1
00 OFF 1 ON 1
01 OFF 2 ON 2
02 OFF 3 ON 3
03 Coasting stop
04 Quick stop
05 Freeze outp. freq.
06 Ramp stop Start
07 Reset
08 Bus jog 1
09 Bus jog 2
10 Data not valid Data not valid
11 Slow down
12 Catch-up
13 Select Setup (lsb)
14 Select Setup (msb)
15 Reversing
Bit 00-01-02, OFF1-2-3/ON1-2-3:
Bit 00-01-02 = 0 causes ramp stop, which uses the
ramp time in parameters 207/208 or 209/210.
If Relay 123 is selected in parameter 323 Relay out-
put, the output relay will be activated when the
output frequency is 0 Hz.
Bit 00-01-02 = 1 means that the frequency con-
verter can start the motor if the other starting
conditions are fullled.
B
it 03, Coasting stop:
See description under Control word according to FC
protocol.
B
it 04, Quick stop:
See description under Control word according to FC
protocol.
B
it 05, Freeze output frequency:
See description under Control word according to FC
protocol.
B
it 06, Ramp stop/start:
See description under Control word according to FC
protocol.
B
it 07, Reset:
See description under Control word according to FC
protocol.
B
it 08, Jog 1:
Bit 08 = "1" means that the output frequency is de-
termined by parameter 09 Bus jog 1.
B
it 09, Jog 2:
Bit 09 = "1" means that the output frequency is de-
termined by parameter 510 Bus jog 2.
B
it 10, Data not valid/Data valid:
See description under Control word according to FC
protocol.
B
it 11, Slow-down:
Used to reduce the speed reference by the value in
parameter 219 Catch-up/slow-down reference.
Bit 11 = 0 does not cause any change to the refer-
ence.
Bit 11 = 1 means that the reference is reduced.
B
it 12, Catch-up:
Used to increase the speed reference by the value in
parameter 219 Catch-up/slow-down reference.
Bit 12 = 0 does not cause any change to the refer-
ence.
Bit 12 = 1 means that the reference is increased.
If both Slow down and Catch-up are activated (Bits
11 and 12 = "1"), slow down has the highest priority,
i.e. that the speed reference is reduced.
B
it 13/14, Selection of Setup:
See description under Control word according to FC
protocol.
B
it 15 Reversing:
See description under Control word according to FC
protocol.
MG.04.A1.02 - VLT is a registered Danfoss trade mark
103
Programming

Table of Contents

Other manuals for Danfoss VLT FCD 322

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FCD 322 and is the answer not in the manual?

Danfoss VLT FCD 322 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FCD 322
CategoryDC Drives
LanguageEnglish

Related product manuals