VLT
®
FCD Series
Serial communication reference
The serial communication reference is transferred to
the frequency converter as a 16-bit word. The value
is transferred in whole numbers 0 - ±32767 (±200%).
16384 (4000 Hex) corresponds to 100%.
The serial communication reference has the follow-
ing format: 0-16384 (4000 Hex)
=
0-100% (Par. 204
Minimum ref. - Par. 205 Maximum ref.).
It is possible to change the direction of rotation via
the serial reference. This is done by converting the
binary reference value to 2 complement. See exam-
ple.
E
xample - Control word and serial communication
r
ef.:
The frequency converter is to receive a start com-
mand and the reference is to be set to 50% (2000
Hex) of the reference range.
Control word = 047F Hex Start command.
Reference = 2000 Hex 50% reference.
The frequency converter is to receive a start com-
mand and the reference is to be set to -50% (-2000
Hex) of the reference range.
The reference value is rst converted to 1 comple-
ment, and then 1 is added binarily to obtain 2
complement:
2000 Hex 0010 0000 0000 0000 0000
1 complement 1101 1111 1111 1111 1111
+1
2 complement 1110 0000 0000 0000 0000
Control word = 047F Hex Start command.
Reference = E000 Hex -50% reference.
Present output frequency
The value of the frequency converters present out-
put frequency is transferred as a 16-bit word. The
value is transferred as whole numbers 0 - ±32767
(±200%).
16384 (4000 Hex) corresponds to 100%.
Output frequency has the following format:
0-16384 (4000 Hex)
=
0-100% (Par. 201 Output fre-
quency low limit - Par. 202 Output frequency high
limit).
E
xample - Status word and current output frequency:
The master receives a status message from the fre-
quency converter that the current output frequency is
50% of the output frequency range.
Par. 201 Output frequency low limit =0Hz
Par. 202 Output frequency high limit =50Hz
Status word = 0F03 Hex.
Output frequency= 2000 Hex 50% of the fre-
quency range, corresponding to 25 Hz.
MG.04.A1.02 - VLT is a registered Danfoss trade mark
105
Programming

Table of Contents

Other manuals for Danfoss VLT FCD 322

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FCD 322 and is the answer not in the manual?

Danfoss VLT FCD 322 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FCD 322
CategoryDC Drives
LanguageEnglish

Related product manuals