Relay output
Programmable relay output 1
Relay 01 Terminal number 01-03 (break), 01-02 (make)
Max. terminal load (AC-1)
1)
on 01-02 (NO) (resistive load) 250 V AC, 2 A
Max. terminal load (AC-15)
1)
on 01-02 (NO) (Inductive load @ cosφ 0.4) 250 V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 01-02 (NO) (resistive load) 30 V DC, 2 A
Max. terminal load (DC-13)
1)
on 01-02 (NO) (inductive load) 24 V DC, 0.1 A
Max. terminal load (AC-1)
1)
on 01-03 (NC) (resistive load) 250 V AC, 2 A
Max. terminal load (AC-15)
1)
on 01-03 (NC) (Inductive load @ cosφ 0.4) 250 V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 01-03 (NC) (resistive load) 30 V DC, 2 A
Min. terminal load on 01-03 (NC), 01-02 (NO) 24 V DC 10 mA, 24 V AC 20 mA
Environment according to EN 60664-1 Overvoltage category III/pollution degree 2
1)
IEC 60947 part 4 and 5
Control card, 10 V DC output
Terminal number 50
Output voltage 10.5 V ±0.5 V
Max. load 25 mA
NOTICE!
All inputs, outputs, circuits, DC supplies and relay contacts are galvanically isolated from the supply voltage (PELV) and
other high-voltage terminals.
Surroundings
Enclosure IP20
Enclosure kit available. IP21, TYPE 1
Vibration test 1.0 g
Max. relative humidity 5–95% (IEC 60721-3-3); Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60721-3-3), coated class 3C3
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature Max. 104°F [40°C]
Derating for high ambient temperature, see chapter 1.9.1 Derating for Ambient Temperature
Minimum ambient temperature during full-scale operation 32°F [0°C]
Minimum ambient temperature at reduced performance 14° [-10°C]
Temperature during storage/transport -13°–+149/158°F [-25°–+65/70°C]
Maximum altitude above sea level without derating 3300 ft [1000 m]
Maximum altitude above sea level with derating 10,000 ft [3000 m]
Derating for high altitude, see chapter 1.9 Special Conditions
Safety standards EN/IEC 61800-5-1, UL 508C
EMC standards, Emission EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, Immunity
EN 61800-3, EN 61000-6-1/2, EN 61000-4-2, EN 61000-4-3,
EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
See chapter 1.9 Special Conditions