3 Electrical Installation
3.1 How to Connect
3.1.1 Electrical Installation in General
NB!
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper conductors
required, (60-75° C) recommended.
Details of terminal tightening torques.
Power (kW) Torque (Nm)
Frame
1 x 200-240
V
3 x 200-240
V
3 x 380-480
V
Line Motor
DC connec-
tion/Brake
1)
Control Ter-
minals
Earth Relay
M1 0.18 - 0.75 0.25 - 0.75 0.37 - 0.75 1.4 0.7 - 0.15 3 0.5
M2 1.5 1.5 1.5 - 2.2 1.4 0.7 - 0.15 3 0.5
M3 2.2 2.2 - 3.7 3.0 - 7.5 1.4 0.7 - 0.15 3 0.5
1)
Spade connectors (6.3 mm Faston plugs)
Table 3.1: Tightening of terminals.
3.1.2 Fuses
Branch circuit protection:
In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines etc., must be short-circuited
and overcurrent protected according to national/international regulations.
Short circuit protection:
Danfoss recommends using the fuses mentioned in the following tables to protect service personnel or other equipment in case of an internal failure in
the unit or short-circuit on DC-link. The frequency converter provides full short circuit protection in case of a short-circuit on the motor or brake output.
a circuit capable of supplying a maximum of 100,000 A
rms
(symmetrical), 480 V maximum.
Overcurrent protection:
Provide overload protection to avoid overheating of the cables in the installation. Overcurrent protection must always be carried out according to national
regulations. Fuses must be designed for protection in a circuit capable of supplying a maximum of 100,000 A
rms
(symmetrical), 480 V maximum.
Non UL compliance:
If UL/cUL is not to be complied with, Danfoss recommends using the fuses mentioned in the below table, which will ensure compliance with EN50178/
IEC61800-5-1:
In case of malfunction, not following the fuse recommendation may result in damage to the frequency converter.
VLT
®
Micro Drive FC 51 Operating Instructions 3 Electrical Installation
MG.02.A4.02 - VLT
®
is a registered Danfoss trademark
11
3

Table of Contents

Other manuals for Danfoss VLT Micro Drive FC 51 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Micro Drive FC 51 Series and is the answer not in the manual?

Danfoss VLT Micro Drive FC 51 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT Micro Drive FC 51 Series
CategoryMedia Converter
LanguageEnglish

Related product manuals