Bit 03, Coasting:
Bit 03 = “0” shuts off the output transistors causing the motor to coast to a standstill.
Bit 03 = “1” enables the frequency converter to start the motor if the other starting conditions have been fulfilled.
NB!
In par. 8-50
Coasting select
a selection is made to define how Bit 03 gates with the corresponding function on a digital input.
Bit 04, Quick stop:
Bit 04 = “0” causes a stop, in which the motor speed is ramped down to stop via 9ar. 3-81
Quick stop ramp time
.
Bit 05, Hold output frequency:
Bit 05 = “0” causes the present output frequency (in Hz) to freeze. The frozen output frequency can then be changed only by means of the digital inputs
(par. 5-10 to 5-15) programmed to
Speed up
and
Speed down
.
NB!
If
Freeze output
is active, the frequency converter can only be stopped by the following:
Bit 03 Coasting stop
Bit 02 DC braking
Digital input (par. 5-10 to 5-15) programmed to
DC braking
,
Coasting stop
or
Reset and coasting stop.
Bit 06, Ramp stop/start:
Bit 06 = “0” causes a stop, in which the motor speed is ramped down to stop via the selected ramp down parameter.
Bit 06 = “1” permits the frequency converter to start the motor, if the other starting conditions have been fulfilled.
NB!
In par. 8-53
Start select
a selection is made to define how Bit 06
Ramp stop/start
gates with the corresponding function on a digital
input.
Bit 07, Reset:
Bit 07 = “0” does not cause a reset.
Bit 07 = “1” causes the reset of a trip. Reset is activated on the signal's leading edge, i.e. when changing from logic “0” to logic “1”.
Bit 08, Jog:
Bit 08 = “1” causes the output frequency to be determined by par. 3-19
Jog speed
.
Bit 09, Selection of ramp 1/2:
Bit 09 = “0” means the ramp 1 is active (par. 3-40 to 3-47).
Bit 09 = ”1” means that ramp 2 (par. 3-50 to 3-57) is active.
Bit 10, Data not valid/Data valid:
Is used to tell the frequency converter whether the control word is to be used or ignored.
Bit 10 = “0” causes the control word to be ignored.
Bit 10 =”1” causes the control word to be used.
Bit 11, Relay 01:
Bit 11 = “0” Relay 01 not activated
Bit 11 = “1” Relay 01 is activated, provided
Control word Bit 11
has been chosen in par. 5-40
Function relay
.
5 Modbus RTU VLT
®
Micro Drive FC 51 Operating Instructions
36
MG.02.A4.02 - VLT
®
is a registered Danfoss trademark
5

Table of Contents

Other manuals for Danfoss VLT Micro Drive FC 51 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Micro Drive FC 51 Series and is the answer not in the manual?

Danfoss VLT Micro Drive FC 51 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT Micro Drive FC 51 Series
CategoryMedia Converter
LanguageEnglish

Related product manuals