4-6X Speed Bypass
4-61 Bypass Speed From [Hz]
0.0 - 400.0Hz * 0.0Hz
4-63 Bypass Speed To [Hz]
0.0 - 400.0Hz * 0.0Hz
5-1X Digital Inputs
5-10 Terminal 18 Digital Input
[0] No function
[1] Reset
[2] Coast inverse
[3] Coast and reset inv.
[4] Quick stop inverse
[5] DC-brake inv.
[6] Stop inv
*[8] Start
[9] Latched start
[10] Reversing
[11] Start reversing
[12] Enable start forward
[13] Enable start reverse
[14] Jog
[16-18] Preset ref bit 0-2
[19] Freeze reference
[20] Freeze output
[21] Speed up
[22] Speed down
[23] Setup select bit 0
[28] Catch up
[29] Slow down
[34] Ramp bit 0
[60] Counter A (up)
[61] Counter A (down)
[62] Reset counter A
[63] Counter B (up)
[64] Counter B (down)
[65] ResetCounter B
5-11 Terminal 19 Digital Input
See par. 5-10. * [10] Reversing
5-12 Terminal 27 Digital Input
See par. 5-10. * [1] Reset
5-13 Terminal 29 Digital Input
See par. 5-10. * [14] Jog
5-15 Terminal 33 Digital Input
See par. 5-10. * [16] Preset ref bit 0
[26] Precise Stop Inverse
[27] Start, Precise Stop
[32] Pulse Input
5-4X Relays
5-40 Function Relay
*[0] No opreation
[1] Control ready
[2] Drive ready
[3] Drive ready, Remote
[4] Enable / No warning
[5] Drive running
[6] Running / No warning
[7] Run in range / No warning
[8] Run on ref / No warning
[9] Alarm
[10] Alarm or warning
[12] Out of current range
[13] Below current, low
[14] Above current, high
[21] Thermal warning
[22] Ready, No thermal warning
[23] Remote ready, No thermal
warning
[24] Ready, Voltage ok
[25] Reverse
[26] Bus ok
[28] Brake,NoWarn
[29] Brake ready/NoFault
[30] BrakeFault (IGBT)
[32] Mech.brake control
[36] Control word bit 11
[51] Local ref. active
[52] Remote ref. active
[53] No alarm
[54] Start cmd active
[55] Running reverse
[56] Drive in hand mode
[57] Drive in auto mode
[60-63] Comparator 0-3
[70-73] Logic rule 0-3
[81] SL digital output B
5-5X Pulse Input
5-55 Terminal 33 Low Frequency
20 - 4999Hz * 20Hz
5-56 Terminal 33 High Frequency
21 - 5000Hz * 5000Hz
5-57 Term. 33 Low Ref./Feedb.
Value
-4999 - 4999 * 0.000
5-58 Term. 33 High Ref./Feedb.
Value
-4999 - 4999 * 50.000
6-XX Analog In/Out
6-0X Analog I/O Mode
6-00 Live Zero Timeout Time
1 - 99s * 10s
6-01 Live Zero TimeoutFunction
*[0] Off
[1] Freeze output
[2] Stop
[3] Jogging
[4] Max speed
[5] Stop and trip
6-1X Analog Input 1
6-10 Terminal 53 Low Voltage
0.00 - 9.99V * 0.07V
6-11 Terminal 53 High Voltage
0.01 - 10.00V * 10.00V
6-12 Terminal 53 Low Current
0.00 - 19.99mA * 0.14mA
6-13 Terminal 53 High Current
0.01 - 20.00mA * 20.00mA
6-14 Term. 53 Low Ref./Feedb.
Value
-4999 - 4999 * 0.000
6-15 Term. 53 High Ref./Feedb.
Value
-4999 - 4999 * 50.000
6-16 Terminal 53 Filter Time
Constant
0.01 - 10.00s * 0.01s
6-19 Terminal 53 mode
*[0] Voltage mode
[1] Current mode
6-2X Analog Input 2
6-22 Terminal 60 Low Current
0.00 - 19.99mA * 0.14mA
6-23 Terminal 60 High Current
0.01 - 20.00mA * 20.00mA
6-24 Term. 60 Low Ref./Feedb.
Value
-4999 - 4999 * 0.000
6-25 Term. 60 High Ref./Feedb.
Value
-4999 - 4999 * 50.00
6-26 Terminal 60 Filter Time
Constant
0.01 - 10.00s * 0.01s
6-8X LCP potentiometer
6-80 LCP Potmeter Enable
[0] Disabled
*[1] Enable
6-81 LCP potm. Low Reference
-4999 - 4999 * 0.000
6-82 LCP potm. High Reference
-4999 - 4999 * 50.00
6-9X Analog Output xx
6-90 Terminal 42 Mode
*[0] 0-20mA
[1] 4-20mA
[2] Digital Output
6-91 Terminal 42 Analog Output
*[0] No operation
[10] Output Frequency
[11] Reference
[12] Feedback
[13] Motor Current
[16] Power
[20] Bus Reference
6-92 Terminal 42 Digital Output
See par. 5-40
*[0] No Operation
[80] SL Digital Output A
6-93 Terminal 42 Output Min Scale
0.00 - 200.0% * 0.00%
6-94 Terminal 42 Output Max Scale
0.00 - 200.0% * 100.0%
7-XX Controllers
7-2X Process Ctrl. Feedb
7-20 Process CL Feedback 1
Resource
*[0] NoFunction
[1] Analog Input 53
[2] Analog input 60
[8] PulseInput33
[11] LocalBusRef
7-3X Process PI
Ctrl. 7-30 Process PI Normal/
Inverse Ctrl
*[0] Normal
[1] Inverse
7-31 Process PI Anti Windup
[0] Disable
*[1] Enable
7-32 Process PI Start Speed
0.0 - 200.0Hz * 0.0Hz
7-33 Process PI Proportional Gain
0.00 - 10.00 * 0.01
7-34 Process PI Integral Time
0.10 - 9999s * 9999s
7-38 Process PI Feed Forward
Factor
0 - 400% * 0%
7-39 On Reference Bandwidth
0 - 200 % * 5%
8-XX Comm. and Options
8-0X General Settings
8-01 Control Site
*[0] Digital and ControlWord
[1] Digital only
[2] ControlWord only
8-02 Control Word Source
[0] None
*[1] FC RS485
8-03 Control Word Timeout Time
0.1 - 6500s * 1.0s
8-04 Control Word Timeout
Function
*[0] Off
[1] Freeze Output
[2] Stop
[3] Jogging
[4] Max. Speed
[5] Stop and trip
8-06 Reset Control Word Timeout
*[0] No Function
[1] Do reset
8-3X FC Port Settings
8-30 Protocol
*[0] FC
[2] Modbus
8-31 Address
1 - 247 * 1
8-32 FC Port Baud Rate
[0] 2400 Baud
[1] 4800 Baud
*[2] 9600 Baud For choose FC Bus
in 8-30
*[3] 19200 Baud For choose
Modbus in 8-30
[4] 38400 Baud
8-33 FC Port Parity
*[0] Even Parity, 1 Stop Bit
[1] Odd Parity, 1 Stop Bit
[2] No Parity, 1 Stop Bit
[3] No Parity, 2 Stop Bits
8-35 Minimum Response Delay
0.001-0.5 * 0.010s
8-36 Max Response Delay
0.100 - 10.00s * 5.000s
8-4X FC MC protocol set
8-43 FC Port PCD Read Configuration
*[0] None Expressionlimit
[1] [1500] Operation Hours
[2] [1501] Running Hours
[3] [1502] kWh Counter
[4] [1600] Control Word
[5] [1601] Reference [Unit]
[6] [1602] Reference %
[7] [1603] Status Word
[8] [1605] Main Actual Value [%]
[9] [1609] Custom Readout
[10] [1610] Power [kW]
[11] [1611] Power [hp]
[12] [1612] Motor Voltage
[13] [1613] Frequency
[14] [1614] Motor Current
[15] [1615] Frequency [%]
[16] [1618] Motor Thermal
[17] [1630] DC Link Voltage
[18] [1634] Heatsink Temp.
[19] [1635] Inverter Thermal
[20] [1638] SL Controller State
[21] [1650] External Reference
[22] [1651] Pulse Reference
[23] [1652] Feedback [Unit]
[24] [1660] Digital Input 18,19,27,33
[25] [1661] Digtial Input 29
[26] [1662] Analog Input 53(V)
[27] [1663] Analog Input 53(mA)
[28] [1664] Analog Input 60
[29] [1665] Analog Output 42 [mA]
[30] [1668] Freq. Input 33 [Hz]
[31] [1671] Relay Output [bin]
[32] [1672] Counter A
[33] [1673] Counter B
[34] [1690] Alarm Word
[35] [1692] Warning Word
[36] [1694] Ext. Status Word
Quick Guide VLT Micro Drive Quick Guide
MG.02.B6.02 - VLT
®
is a registered Danfoss trademark 11
1 1

Other manuals for Danfoss VLT Micro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Micro and is the answer not in the manual?

Danfoss VLT Micro Specifications

General IconGeneral
BrandDanfoss
ModelVLT Micro
CategoryMedia Converter
LanguageEnglish

Related product manuals