1.5 Parameter Overview
Parameter Overwiev
0-XX Operation/Display
0-0X Basic Settings
0-03 Regional Settings
*[0] International
[1] US
0-04 Oper. State at Power-up
(Hand)
[0] Resume
*[1] Forced stop, ref = old
[2] Forced stop, ref = 0
0-1X Set-up Handling
0-10 Active Set-up
*[1] Setup 1
[2] Setup 2
[9] Multi Setup
0-11 Edit Set-up
*[1] Setup 1
[2] Setup 2
[9] Active Setup
0-12 Link Setups
[0] Not Linked
*[20] Linked
0-31 Custom Readout Min Scale
0.00 9999.00 * 0.00
0-32 Custom Readout Max Scale
0.00 9999.00 * 100.0
0-4X LCP Keypad
0-40 [Hand on] Key on LCP
[0] Disabled
*[1] Enabled
0-41 [Off / Reset] Key on LCP
[0] Disable All
*[1] Enable All
[2] Enable Reset Only
0-42 [Auto on] Key on LCP
[0] Disabled
*[1] Enabled
0-5X Copy/Save
0-50 LCP Copy
*[0] No copy
[1] All to LCP
[2] All from LCP
[3] Size indep. from LCP
0-51 Set-up Copy
*[0] No copy
[1] Copy from setup 1
[2] Copy from setup 2
[9] Copy from Factory setup
0-6X Password
0-60 (Main) Menu Password
0-999 *0
0-61 Access to Main/Quick Menu
w/o Password
*[0] Full access
[1] LCP:Read Only
[2] LCP:No Access
1-XX Load/Motor
1-0X General Settings
1-00 Configuration Mode
*[0] Speed open loop
[3] Process
1-01 Motor Control Principle
[0] U/f
*[1] VVC+
1-03 Torque Characteristics
*[0] Constant torque
[2] Automatic Energy Optim.
1-05 Local Mode Configuration
[0] Speed Open Loop
*[2] As config in par. 1-00
1-2X Motor Data
1-20 Motor Power [kW] [HP]
[1] 0.09kW/0.12HP
[2] 0.12kW/0.16HP
[3] 0.18kW/0.25HP
[4] 0.25kW/0.33HP
[5] 0.37kW/0.50HP
[6] 0.55kW/0.75HP
[7] 0.75kW/1.00HP
[8] 1.10kW/1.50HP
[9] 1.50kW/2.00HP
[10] 2.20kW/3.00HP
[11] 3.00kW/4.00HP
[12] 3.70kW/5.00HP
[13] 4.00kW/5.40HP
[14] 5.50kW/7.50HP
[15] 7.50kW/10.00HP
[16] 11.00kW/15.00HP
[17] 15.00kW/20.00HP
[18] 18.50kW/25.00HP
[19] 22.00kW/29.50HP
[20] 30.00kW/40.00HP
1-22 Motor Voltage
50 - 999V * 230 - 400V
1-23 Motor Frequency
20 - 400Hz * 50Hz
1-24 Motor Current
0.01 - 100.00A * Motortype dep.
1-25 Motor Nominal Speed
100 - 9999rpm * Motortype dep.
1-29 Automatic Motor Tuning
(AMT)
*[0] Off
[2] Enable AMT
1-3X Adv. Motor Data
1-30 Stator Resistance (Rs)
[Ohm] * Dep. on motor data
1-33 Stator Leakage Reactance (X1)
[Ohm] * Dep. on motor data
1-35 Main Reactance (Xh)
[Ohm] * Dep. on motor data
1-5X Load Indep. Setting
1-50 Motor Magnetisation at 0
Speed
0 - 300 % * 100 %
1-52 Min Speed Norm. Magnet. [Hz]
0.0 - 10.0Hz * 0.0Hz
1-55 U/f Characteristic - U
0 - 999.9V
1-56 U/f Characteristic - F
0 - 400Hz
1-6X Load Depen. Setting
1-60 Low Speed Load Compen-
sation
0 - 199% * 100%
1-61 High Speed Load Compen-
sation
0 - 199% * 100%
1-62 Slip Compensation
-400 - 399% * 100%
1-63 Slip Compensation Time
Constant
0.05 - 5.00s * 0.10s
1-7X Start Adjustments
1-71 Start Delay
0.0 - 10.0s * 0.0s
1-72 Start Function
[0] DC hold / delay time
[1] DC brake / delay time
*[2] Coast / delay time
1-73 Flying Start
*[0] Disabled
[1] Enabled
1-8X Stop Adjustments
1-80 Function at Stop
*[0] Coast
[1] DC hold
1-82 Min Speed for Funct. at Stop
[Hz]
0.0 - 20.0 Hz * 0.0 Hz
1-9XMotor Temperature
1-90 Motor Thermal Protection
*[0] No protection
[1] Termistor warning
[2] Thermistor trip
[3] Etr warning
[4] Etr trip
1-93 Thermistor Resource
*[0] None
[1] Analog input 53
[6] Digital input 29
2-XX Brakes
2-0XDC-Brake
2-00 DC Hold Current
0 - 150% * 50%
2-01 DC Brake Current
0 - 150% * 50%
2-02 DC Braking Time
0.0 - 60.0s * 10.0s
2-04 DC Brake Cut In Speed
0.0 - 400.0Hz * 0.0Hz
2-1X Brake Energy Funct.
2-10 Brake Function
*[0] Off
[1] Resistor brake
[2] AC brake
2-11 Brake Resistor (ohm)
5 - 5000 * 5
2-16 AC Brake, Max current
0 - 150 % * 100%
2-17 Over-voltage Control
*[0] Disabled
[1] Enabled (not at stop)
[2] Enabled
2-2* Mechanical Brake
2-20 Release Brake Current
0.00 - 100.0A * 0.00A
2-22 Activate Brake Speed [Hz]
0.0 - 400.0Hz * 0.0Hz
3-XX Reference / Ramps
3-0X Reference Limits
3-00 Reference Range
*[0] Min - Max
[1] -Max - +Max
3-02 Minimum Reference
-4999 - 4999 * 0.000
3-03 Maximum Reference
-4999 - 4999 * 50.00
3-1X References
3-10 Preset Reference
-100.0 - 100.0% * 0.00%
3-11 Jog Speed [Hz]
0.0 - 400.0Hz * 5.0Hz
3-12 Catch up/slow Down Value
0.00 - 100.0% * 0.00%
3-14 Preset Relative Reference
-100.0 - 100.0 % * 0.00 % 3-15
Reference Resource 1
[0] No function
*[1] Analog Input 53
[2] Analog input 60
[8] Pulse input 33
[11] Local bus ref
[21] LCP Potentiometer
3-16 Reference Resource 2
[0] No function
[1] Analog Input 53
*[2] Analog input 60
[8] Pulse input 33
*[11] Local bus ref
[21] LCP Potentiometer
3-17 Reference Resource 3
[0] No function
[1] Analog Input 53
[2] Analog input 60
[8] Pulse input 33
*[11] Local bus ref
[21] LCP Potentiometer
3-18 Relative Scaling Ref. Resource
*[0] No function
[1] Analog Input 53
[2] Analog input 60
[8] Pulse input 33
[11] Local bus ref
[21] LCP Potentiometer
3-4X Ramp 1
3-40 Ramp 1 Type
*[0] Linear
[2] Sine2 ramp
3-41 Ramp 1 Ramp up Time
0.05 - 3600s * 3.00s (10.00s
1)
)
3-42 Ramp 1 Ramp Down Time
0.05 - 3600s * 3.00s (10.00s
1)
)
3-5X Ramp 2
3-50 Ramp 2 Type
*[0] Linear
[2] Sine2 ramp
3-51 Ramp 2 Ramp up Time
0.05 - 3600s * 3.00s (10.00 s
1)
)
3-52 Ramp 2 Ramp down Time
0.05 - 3600s * 3.00s (10.00 s
1)
)
3-8X Other Ramps
3-80 Jog Ramp Time
0.05 - 3600s * 3.00s (10.00s
1)
)
3-81 Quick Stop Ramp Time
0.05 - 3600s * 3.00s (10.00s
1)
)
4-XX Limits / Warnings
4-1X Motor Limits
4-10 Motor Speed Direction
[0] Clockwise
[1] CounterClockwise
*[2] Both
4-12 Motor Speed Low Limit [Hz]
0.0 - 400.0Hz * 0.0Hz
4-14 Motor Speed High Limit [Hz]
0.1 - 400.0 Hz * 65.0 Hz
4-16 Torque Limit Motor Mode
0 - 400 % * 150 %
4-17 Torque Limit Generator Mode
0 - 400% * 100%
4-5X Adj. Warnings
4-50 Warning Current Low
0.00 - 100.00A * 0.00A
4-51 Warning Current High
0.00 - 100.00A * 100.00A
4-58 Missing Motor Phase Function
[0] Off
*[1] On
1)
M4 and M5 only
Quick Guide VLT Micro Drive Quick Guide
10 MG.02.B6.02 - VLT
®
is a registered Danfoss trademark
11

Other manuals for Danfoss VLT Micro