1.8 General Technical Data
Protection and features
Electronic thermal motor protection against overload.
Temperature monitoring of the heatsink ensures that the frequency converter trips in case of overtemperature.
The frequency converter is protected against short-circuits between motor terminals U, V, W.
If a motor phase is missing, the frequency converter trips and issues an alarm.
If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).
Monitoring of the intermediate circuit voltage ensures that the frequency converter trips if the intermediate circuit
voltage is too low or too high.
The frequency converter is protected against earth faults on motor terminals U, V, W.
Mains supply (L1/L, L2, L3/N):
Supply voltage 200-240V ±10%
Supply voltage 380-480V ±10%
Supply frequency 50/60Hz
Max. imbalance temporary between mains phases 3.0% of rated supply voltage
True Power Factor (λ) 0.4 nominal at rated load
Displacement Power Factor (cosφ) near unity (> 0.98)
Switching on input supply L1/L, L2, L3/N (power-ups) maximum 2 times/min.
Environment according to EN60664-1 overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 240/480V
maximum.
Motor output (U, V, W):
Output voltage 0 - 100% of supply voltage
Output frequency 0-200Hz (VVC+), 0-400Hz (u/f)
Switching on output Unlimited
Ramp times 0.05 - 3600sec.
Cable lengths and cross sections:
Max. motor cable length, screened/armoured (EMC correct installation) 15m
Max. motor cable length, unscreened/unarmoured 50m
Max. cross section to motor, mains*
Connection to load sharing/brake (M1, M2, M3) 6.3mm insulated Faston Plugs
Max. cross section to load sharing/brake (M4, M5) 16mm
2
/6AWG
Maximum cross section to control terminals, rigid wire 1.5mm
2
/16 AWG (2 x 0.75mm
2
)
Maximum cross section to control terminals, flexible cable 1mm
2
/18 AWG
Maximum cross section to control terminals, cable with enclosed core 0.5mm
2
/20AWG
Minimum cross section to control terminals 0.25mm
2
* See tables for mains supply for more information!
Digital Inputs (Pulse/Enocder Inputs):
Programmable digital inputs (Pulse/encoder) 5 (1)
Terminal number 18, 19, 27, 29, 33,
Logic PNP or NPN
Voltage level 0 - 24V DC
Voltage level, logic'0' PNP < 5V DC
Voltage level, logic'1' PNP > 10V DC
Voltage level, logic '0' NPN > 19V DC
Voltage level, logic '1' NPN < 14V DC
Maximum voltage on input 28V DC
Input resistance, R
i
approx. 4k
Max. pulse frequency at terminal 33 5000Hz
Min. pulse frequency at terminal 33 20Hz
Quick Guide VLT Micro Drive Quick Guide
16 MG.02.B6.02 - VLT
®
is a registered Danfoss trademark
11

Other manuals for Danfoss VLT Micro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Micro and is the answer not in the manual?

Danfoss VLT Micro Specifications

General IconGeneral
BrandDanfoss
ModelVLT Micro
CategoryMedia Converter
LanguageEnglish

Related product manuals