EasyManuals Logo
Home>Danfoss>DC Drives>VLT Midi Drive FC 280

Danfoss VLT Midi Drive FC 280 Instruction Manual

Danfoss VLT Midi Drive FC 280
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #21 background imageLoading...
Page #21 background image
4.9 Installation Checklist
Before completing installation of the unit, inspect the entire installation as detailed in Table 4.3. Check and mark the items
when completed.
Inspect for Description
Auxiliary equipment
Look for auxiliary equipment, switches, disconnects or input fuses/circuit breakers, which may reside on
the input power side of the frequency converter or output side to the motor. Ensure that they are ready
for full-speed operation.
Check the function and installation of any sensors used for feedback to the adjustable frequency drive.
Remove any power factor correction capacitors on the motor(s).
Adjust any power factor correction capacitors on the line power side and ensure that they are dampened.
Cable routing
Ensure that the motor wiring and control wiring are separated, screened or in 3 separate metallic conduits
for high-frequency interference isolation.
Control wiring
Check for broken or damaged wires and loose connections.
Check that the control wiring is isolated from power and motor wiring for noise immunity.
Check the voltage source of the signals, if necessary.
The use of shielded cable or twisted pair is recommended. Ensure that the shield is terminated correctly.
Cooling clearance
Ensure that the top and bottom clearance is adequate to ensure proper air ow for cooling, see
chapter 3.3 Mounting.
Ambient conditions
Check that requirements for ambient conditions are met.
Fusing and circuit
breakers
Check for proper fusing or circuit breakers.
Check that all fuses are inserted rmly and are in operational condition and that all circuit breakers are in
the open position.
Grounding
Check for sucient ground connections and ensure that they are tight and free of oxidation.
Do not ground to conduit or mount the back panel to a metal surface.
Input and output
power wiring
Check for loose connections.
Check that the motor and line cables are in separate conduit or separated shielded cables.
Panel interior
Inspect that the unit interior is free of dirt, metal chips, moisture and corrosion.
Check that the unit is mounted on an unpainted, metal surface.
Switches
Ensure that all switch and disconnect settings are in the proper positions.
Vibration
Check that the unit is mounted solidly or that shock mounts are used, as necessary.
Check for an unusual amount of vibration.
Table 4.3 Installation Check List
CAUTION
POTENTIAL HAZARD IN THE EVENT OF INTERNAL FAILURE
Risk of personal injury if the adjustable frequency drive is not properly closed.
Before applying power, ensure that all safety covers are in place and securely fastened.
Electrical Installation Instruction Manual
MG07A122 Danfoss A/S © 11/2015 All rights reserved. 19
4 4

Table of Contents

Other manuals for Danfoss VLT Midi Drive FC 280

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Midi Drive FC 280 and is the answer not in the manual?

Danfoss VLT Midi Drive FC 280 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Midi Drive FC 280
CategoryDC Drives
LanguageEnglish

Related product manuals