Technical documentation 20140208BA
AFMS3000
Tel.: +49 (0)4105 / 65 600 * DECKMA GmbH * Fax: +49 (0)4105 / 65 60 – 25
Email: info@deckma-gmbh.de * Internet: www.deckma-gmbh.de
Operating instructions
Version 1.0 2018/03/17 page 15 of 24
2.7.2. Faults
In case of a fault, the "FAULT" field illuminates yellow, the acoustic sounder sounds alternatively and
the relay at output JP10 on the main module drops to off. Should the system be in the main menu, it
jumps automatically to the menu tab "New Fault". Information about the new fault is shown in the
display.
FAULT
Pressing the "FAULT"/"A" key silences the acoustic sounder. The display is renewed. Should the
system not yet be in the menu tab "New Fault", this is now shown (e.g. when a new fault occurs while
the user is navigating in the sub-menus).
FAULT
A
Pressing the "FAULT"/"A" key accepts all displayed faults. With the accepting of a fault, the user
signals that the fault has been acknowledged and corresponding measures have been introduced to
remedy it. When all faults have been accepted, the "FAULT" field illuminates once more permanently
yellow.
If more faults have accumulated than the five that can be shown, it is possible to switch between the
faults by pressing the ">>>" menu key. The display is switched from showing a fire alarm to a fault by
pressing the "FIRE"/"A" or "FAULT"/"A" key. The display always shows the newest and the oldest fire
alarm and the newest and oldest fault for 30 s after the last interaction.
Resetting a fault must be undertaken out of the menu entry "Accepted Fault" (repeated pressing of the
"FAULT"/"A" key). In this menu entry, all accepted faults are shown. Pressing the "RESET" key now
only resets the fault selected with an arrow.
After the successful resetting of all faults, the "FAULT" symbol illuminated green again and the relay at
output JP10 of the main module picks up again (common status contact).
If the power supply (mains or emergency supply) fails, the "MAINS" field illuminates yellow. After a
configurable time, a fault also occurs.(shown in the display + blinking "FAULT" field). If both power
supplies are restored, the "MAINS" field turns green again. If the power supply fails completely (also
the emergency battery), the AFMS switches off completely. This means that all relays of the modules
and also the relay behind the "JP10" drop out!
2.8. Operation functions
The main menu can be reached from any sub-menu by pressing the "HOME" key. Pressing the
"BACK" key returns to the previous menu tab, not to the main menu.

Table of Contents

Questions and Answers: