EasyManuals Logo
Home>Dell>Switch>EMC PowerSwitch Z9432F-ON

Dell EMC PowerSwitch Z9432F-ON User Manual

Dell EMC PowerSwitch Z9432F-ON
53 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #12 background imageLoading...
Page #12 background image
Site preparations
The Z9432F-ON switch is suitable for installation as part of a common bond network (CBN).
You can install the switch in:
Network telecommunication facilities
Data centers
Other locations where the National Electric Code (NEC) applies
CAUTION: To avoid tangling cables or damaging optics, install the switch into a rack or cabinet before installing
any additional components such as cables or optics.
Topics:
Site selection
Cabinet placement
Rack mounting
Switch ground
Fans and airflow
Switch power
Storing components
Site selection
Install the switch equipment in restricted access areas.
A restricted access area is one in which service personnel can only gain access using a special tool, lock, key or other means of
security. The authority responsible for the location controls access to the restricted area.
Ensure that the area where you install your switch meets the following safety requirements:
Near an adequate power source. Connect the switch to the appropriate branch circuit protection according to your local
electrical codes.
Switch environmental temperature range is from 0° to 45°C (32° to 113°F).
Relative humidity is from 5 to 90 percent noncondensing.
In a dry, clean, well-ventilated, and temperature-controlled room, away from heat sources such as hot air vents or direct
sunlight
Away from sources of severe electromagnetic noise
Inside the restricted access area that is positioned in a rack or cabinet, or on a desktop with adequate space in the front,
back, and sides for proper ventilation and access
Install the switch in Information Technology Rooms in accordance with Article 645 of the National Electrical Code and NFPA
75.
Install the switch in an environment that meets all region- or country-specific occupational safety and health requirements.
For more information about switch storage and environmental temperatures, see Specifications.
Cabinet placement
Install the Z9432F-ON switch only in indoor cabinets that are designed for use in a controlled environment.
Do not install the switch in outside cabinets. For cabinet placement requirements, see Site selection.
The cabinet must meet minimum size requirements. Airflow must be in accordance with the Electronic Industries Alliance (EIA)
standard. Ensure that there is a minimum of 12.7 cm (5 inches) between the intake and exhaust vents and the cabinet wall.
3
12 Site preparations

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dell EMC PowerSwitch Z9432F-ON and is the answer not in the manual?

Dell EMC PowerSwitch Z9432F-ON Specifications

General IconGeneral
BrandDell
ModelEMC PowerSwitch Z9432F-ON
CategorySwitch
LanguageEnglish

Related product manuals