10.1.2 The Input/Output Mapping Areas
The following table lists the CANopen DS301 specifications for the AS series PLC.
Master
Maximum slave nodes Up to 64 nodes
Maximum transfer size of
a PDO (Read + Write)
Up to 2000 Bytes (including some system configurations)
Slave
Maximum transfer size of
a PDO (Read + Write)
Up to 8 PDOs; each PDO with up to 8 bytes can be transferred
at a time
When the AS Series PLC acts as a Master, the output mapping areas are D25000-D25999, and the input
mapping areas are D24000-D24999, as the following table shows.
D25000–D25031
SDO request information, NMT service information, and
Emergency request information
64 bytes
D24000–D24031 SDO reply information, and Emergency reply information 64 bytes
RxPDO mapping area (Master
TxPDO mapping area (Master
When the AS Series PLC acts as a Slave, the output mapping areas are D25032–25063, and the input
mapping areas are D24032–24063 as the following table shows.
D24032~24063
RxPDO mapping area (Slave
D25032~25063
TxPDO mapping area (Slave