- 2 -
B. DVP28SS2
8
1
2
3
11
12
7
4
5
6
9
13
10
6 0.0 0
6 8.80
9 0.0 0
96. 00
46. 00
8. RS-485 communication port
2. POWER, RUN, ERROR, COM1 and COM2
status indicator
9. Nameplate
5. I/O port for program communication (RS-232)
13. DIN rail mounting slot (35mm)
Electrical Specifications
Model
14SS211R 14SS211T 12SS211S 28SS211R
28SS211T
28SS211S
Power supply voltage
(with counter-connection protection on the polarity of DC input power)
DVPPS01(PS02): input 100-240VAC, output 24VDC/1A(PS02: 2A)
With counter-connection protection on the polarity of DC input power
Free of corrosive gas
Over voltage
1,500VAC (Primary-secondary), 1,500VAC (Primary-PE),
> 5MΩ (all I/O point-to-ground: 500VDC)
Noise immunity
ESD (IEC 61131-2, IEC 61000-4-2): 8kV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2kV, Digital I/O: 1kV,
Analog & Communication I/O: 1kV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Grounding
The diameter of grounding wire cannot be smaller than the wire
diameter of terminals L and N (All DVP units should be grounded
directly to the ground pole).
Operation / storage
Operation: 0°C ~ 55°C (temp.), 5 ~ 95% (humidity), no condensation.
Storage: -25°C ~ 70°C (temp.), 5 ~ 95% (humidity), no condensation.
Vibration / shock
resistance
International standards: IEC61131-2, IEC 68-2-6 (TEST
Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)
Atmospheric
pressure
Operation: 1080 ~ 795hPa (Equivalent to -1000 ~ 2000 feet above sea
level)
Storage: 1080 ~ 660hPa (Equivalent to -1000 ~ 3500 feet above sea
Weight (g) 97g 82.5g 90g