Figure 5-21 : Power vs Frequency parameters
Figure 5-22 : P(V) page
When grid voltage rises up to a lock-in voltage(V lock-in) and inverter’s present
output power is greater than lock-in power(P lock-in), inverter will reduce the
output power and keep it at a certain value(P lock-out) until grid voltage drop
back to lock-out voltage(V lock-out) and passing a certain time(T recovery).
Power Limit
Power vs. Frequency
P(V)
Mode
P lock-in
P lock-out
V lock-in
OFF
20%
5%
253.0V
V lock-out
T recovery
248.4V
300s
EXIT
EXIT
ENT
5.2.8.3 P(V)