Chapter 4 Parameters
VFD-EL-W
4-33
01.00
01.09
01.11
01.10
01.12
Frequency
Time
Accel. Time
Decel. Time
The definition of
Accel./Decel. Time
Max. output
Frequency
setting
operation
frequency
Min. output
frequency
01.05
Resulting
Resulting
Accel. Time
Decel. Time
Resulting Accel./Decel. Time
0 Hz
01.13
Jog Acceleration Time Unit: 0.1/0.01
Settings 0.1–600.0/0.01–600.0 sec.
Default: 1.0
01.14
Jog Deceleration Time Unit: 0.1/0.01
Settings 0.1 to 600.0/0.01 to 600.0 sec. Default: 1.0
01.15
Jog Frequency Unit: 0.01
Settings 0.10 to 400.0 Hz Default: 6.00
Use only external terminal JOG (setting MI2, MI3 or MI4 to 8). When the Jog command is ON, the AC motor
drive accelerates from the Minimum Output Frequency (Pr.01.05) to the Jog Frequency (Pr.01.15). When the
Jog command is OFF, the AC motor drive decelerates from the Jog Frequency to zero. The
acceleration/deceleration time is set by the Jog Acceleration/Deceleration time (Pr.01.13, Pr.01.14).
The drive must be stopped before using the JOG command. During Jog operation, other operation commands
are not accepted, except FORWARD/REVERSE commands.
01.13
01.12
01.21
Frequency
Time
JOG Accel. Time
JOG Decel. Time
The definition of JOG Accel./Decel. Time
01.15
JOG
Frequency
Min. output
frequency
01.05
0 Hz
01.14
01.16
Auto-Acceleration and Auto-Deceleration
Default: 0
Settings 0 Linear acceleration and linear deceleration
1 Auto-acceleration and linear deceleration.