Chapter 7 Optional AccessoriesME300
7-74
File Copy Setting Fault Description
These faults occur when KPC-CC01 cannot perform the command after clicking the ENTER button in the
copy function.
LCM Display * Description Corrective Actions
Parameter and file are read only
The property of the parameter / file is read-only and
cannot be written to.
1. Verify the specification in the user manual.
If the above solution does not work, contact your local
authorized dealer for assistance.
Fail to write parameter and file
An error occurred while writing to a parameter / file.
1. Check for any problem on the Flash IC.
2. Shut down the system, wait for ten minutes, and
then restart the system.
If none of the above solutions work, contact your local
authorized dealer for assistance.
AC drive is in operating status
A setting cannot be changed while motor drive is in
operation.
1. Verify that the drive is not in operation.
If the above solution does not work, contact your local
authorized dealer for assistance.
AC drive parameter is locked
A setting cannot be changed because a parameter is
locked.
1. Check if the parameter is locked or not. If it is
locked, unlock it and try to change the parameter
again.
If the above solution does not work, contact your local
authorized dealer for assistance.
AC drive parameter changing
A setting cannot be changed because a parameter is
being modified.
1. Check if the parameter is being modified. If it is not
being modified, try to change that parameter again.
If the above solution does not work, contact your local
authorized dealer for assistance.
Fault code
A setting cannot be changed because an error has
occurred in the motor drive.
1. Check if there is any error in the motor drive. If
there is not any error, try to change the setting
again.
If the above solution does not work, contact your local
authorized dealer for assistance.
Warning code
A setting cannot be changed because of a warning
message given to the motor drive.
1. Check if there is any warning message given to the
motor drive.
If the above solution does not work, contact your local
authorized dealer for assistance.
File type mismatch
Data to be copied is not the correct type, so the
setting cannot be changed.
1. Check if the products’ serial numbers to be copied
are in the same category. If they are in the same
category, try to change the setting again.
If the above solution does not work, contact your
authorized dealer for assistance.