Chapter 5 Main Circuit TerminalsME300
5-9
Frame D
If you install at Ta 50°C above environment, use copper wires that have a voltage rating of
600 V and are temperature resistant to 90°C or above.
If you install at Ta 50°C environment, use copper wires that have a voltage rating of 600 V
and are temperature resistant to 75°C or 90°C.
For VFD25AME23ANNAA, VFD25AME23ANSAA:
If you install at Ta 45°C above environment, use copper wires that have a voltage rating of
600 V and are temperature resistant to 90°C or above.
To be UL installation compliant, you must use copper wires when installing. The wire gauge
is based on a temperature resistance of 75°C, in accordance with UL requirements and
recommendations.
Do not reduce the wire gauge when using high-temperature resistant wires.
Models
Main Circuit Terminals
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3,
DC-, DC+/+1, +2/B1, B2
Terminals
Max. Wire
Gauge
Min. Wire
Gauge
Screw &
Torque
(±10%)
Max. Wire
Gauge
Min. Wire
Gauge
Screw &
Torque
(±10%)
VFD25AME23ANNAA
10 mm
2
[8 AWG]
10 mm
2
[8 AWG]
M4
20 Kg-cm
[17.4 lb-in.]
[1.96 Nm]
10 mm
2
[8 AWG]
10 mm
2
[8 AWG]
M4
20 Kg-cm
[17.4 lb-in.]
[1.96 Nm]
VFD25AME23ANSAA
VFD13AME43ANNAA
6 mm
2
[10 AWG]
6 mm
2
[10 AWG]
6 mm
2
[10 AWG]
VFD13AME43AFNAA
VFD13AME43ANSAA
VFD13AME43AFSAA
VFD17AME43ANNAA
10 mm
2
[8 AWG]
10 mm
2
[8 AWG]
10 mm
2
[8 AWG]
VFD17AME43AFNAA
VFD17AME43ANSAA
VFD17AME43AFSAA