5
614-06819-00
Technical characteristics
(*) Warning: Output cables should not exceed 10m length.
Eaton 5S 850 1200 1600
•UPS power 850 VA /
510 W
120 VA /
750 W
1600 VA /
1000 W
•Nominal input voltage 185 V - 285 V, adjustable to 150 V - 285 V
•Input frequency 50/60 Hz (46 - 70 Hz working range)
• Voltage/frequency of battery backup
outlets
19
in battery mode
220 V / 230 V / 240 V +15 % -20 % (50/60 Hz ± 1 %)
•Total output current for all outlets 10 A max
• Output current of battery backup
outlets
19
3.8 A max 5.4 A max 7.3 A max
•Leakage current 0.4 mA
•Input protection 10 A resettable circuit breaker
•Transfer time 5 ms typical
•Telephone surge protection Tel, ISDN, ADSL, Ethernet
•Sealed lead-acid battery 12 V, 9 Ah 2 x 12 V, 7 Ah 2 x 12 V, 9 Ah
•Automatic battery test Once a week
•Average battery life 4 years typical, depending on temperature and amount of discharge cycles
•Operating temperature 0 to 35 °C
•Storage temperature -25 °C to +55 °C
•Operating relative humidity 0 to 85 %
•Operating elevation 0 to 2000 m
•Safety standards IEC62040-1,CEcertied
• Electromagnetic compatibility
standards
IEC 62040-2, C1*
AS 62040-2, C1
•Warranty 2 years
•Dimensions (mm) 263 x 81 x 235 305 x 81 x 312
•Weigth (Kg) 3.6 6.7 7. 8