Table 16. Command menu operation
Function
Subfunction
Operation
UPS Control
Commands
Use the or push button to
highlight the desired command function,
then press the push button to
execute the command or proceed to
further command screens.
Normal Mode
Starts the UPS in the standard normal
mode or transfers the UPS from the
bypass mode to the standard normal
mode.
Bypass Mode
Starts the UPS in the bypass mode or
transfers the UPS from the normal
mode to the bypass mode.
High-Efficiency
(HE) Mode
Transfers the UPS from the standard
normal mode to the HE mode.
Transfers the UPS from the HE mode to
the standard normal mode.
Battery Control
Commands
Use the or push button to
highlight the desired command function,
then press the push button to
execute the command.
Charger
Turns the battery charger on.
Resting
Turns the battery charger off.
Table 17. Typical system status messages
Function
Message
UPS
Load Off; Bypass; Online, HE
Bypass
Off; On; Available
Charger
Charger Resting; Charger

Table of Contents