Product Specifications
9-2 Eaton 93E UPS (300/400 kVA, 380/400/415V) Installation and Operation Manual
9.2.2 UPS Output
UPS Output Capacity
100% rated current
Output Voltage Regulation
± 1% (10% to 100% load)
Nominal Output Voltage
380 Vac, 400 Vac and 415 Vac nominal
Output Voltage Harmonic Content 2% maximum THD (linear load)
5% maximum THD (nonlinear load)
Output Current
See Table 3-5.
Output Voltage Balance
< 2% for 100% maximum load imbalance (linear load)
Output Voltage Phase
Displacement
< 2.5° for 100% maximum load imbalance (linear load)
Frequency Regulation
0.1 Hz free running
Synchronous to Bypass
± 4 Hz (default setting)
Frequency Slew Rate
0.1 Hz per second
Load Compatibility 0.9 PF Leading
0.7 PF Lagging
Overload Capability ≦125% for 10 minutes
≦150 % for 30 seconds
≧150% for 150 milliseconds
9.2.3 UPS Environmental
Operating Temperature
0 to 40°C (32 to 104°F) without derating. The recommended operating
temperature is 25°C (77°F).
Operating Altitude
Maximum 1000m (3300 ft) at 30°C without derating
Storage Temperature
-25 to +55°C, excluding batteries (prolonged storage above 40°C causes
rapid battery self-discharge)
Relative Humidity (operating and
storage)
5% to 95% maximum noncondensing
Acoustical Noise
Less than or equal to 74 dB at a 1m distance, per ISO 7779
EMC Meets IEC 62040-2 C3