6. UPS maintenance
6.4 Replacing batteries
DO NOT DISCONNECT the batteries while the UPS is in Battery mode.
Batteries can be replaced easily without turning off the UPS or disconnecting the load.
If you prefer to remove input power to change the batteries, see "UPS Shutdown" on page 32.
Consider all warnings, cautions, and notes before replacing batteries.
• Servicingshouldbeperformedbyqualiedservicepersonnelknowledgeableofbatteriesandrequi-
red precautions. Keep unauthorized personnel away from batteries.
• Batteries can present a risk of electrical shock or burn from high short circuit current.
Observe the following precautions:
1. Remove watches, rings, or other metal objects,
2. Use tools with insulated handles,
3. Do not lay tools or metal parts on top of batteries,
4. Wear rubber gloves and boots.
• When replacing batteries, replace with the same type and number of batteries or battery packs.
Contact your service representative to order new batteries.
• Proper disposal of batteries is required. Refer to your local codes for disposal requirements.
• Neverdisposeofbatteriesinare.Batteriesmayexplodewhenexposedtoame.
• Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes
and may be extremely toxic.
• Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source from
ground. Contact with any part of a grounded battery can result in electrical shock.
The likelihood of such shock can be reduced if such grounds are removed during installation and
maintenance (applicable to equipment and remote battery supplies not having a grounded supply
circuit).
• ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or connectors. Attempting to
alter wiring can cause injury.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
Replacing the internal battery
The internal battery is heavy. Use caution when handling the heavy batteries.
3
5
6
7
2
1
4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton 9PX 1500 RT and is the answer not in the manual?

Eaton 9PX 1500 RT Specifications

General IconGeneral
BrandEaton
Model9PX 1500 RT
CategoryUPS
LanguageEnglish

Related product manuals