Effective 10/2004
Page 47I.L. 70C1036H05
Appendix C Typical Circuit Breaker Master Connection Diagram
AC
AC
AC
AC
AC
AC
K2-1
K2-2
K2-3
K2-4
K2-5
K2-6
K2-7
K2-9
K2-8
Z_COM
Z_IN
Z_OUT
GF _SGND /OFF
N1
N2
J5-10
J5-9
J5-7
1150 POWER RELAY
MODULE
A-13
B-12
B-13
A-7
UVR
B-11
A-8
ST
B-10
B-14
B-15
SC
A-6
A-5
A-4
A-17
SR
A-18
RATING
PLUG
DIGITRIP 1150
DGNDK1-1
ST1K1-2
ST-K1-3
C1K1-5
C2K1-4
B1K1-7
B2K1-6
A1K1-9
A2K1-8
HIGH
INST.
TRIP
MODULE
(WHEN
HIGH INST.
COIL A
COIL B
HIGH INST.
HIGH INST.
COIL C
R/1 CSC
CSBR/1
R/1 CSA
1
B-8
B-7
B-9
B-6
R/1
NEUTRAL1
NEUTRAL2
B-5
B-4
AUX. SWITCH
(OPTIONAL)
L
AB
LL
C
N
SUPPLIED)
J0-13
J0-36
J0-6
J0-5
J0-34
J0-4
J0-3
24 OHMTA
J0-16
J0-39
J0-38
J0-15
J0-14
J0-37
J0-41
J0-18
J0-17
J0-40
J0-43
J0-20
J0-19
J0-42
J0-45
J0-22
J0-21
J0-44
I1-1
I1-2
B-1
B-2
INCOM
INCOM
I1-3
I1-4
I1-6
I1-5
L
C
B
L
L
A
52b
(MCR)
J0-25
J0-26
J0-12J0-29
NN POW
A BUS 2
A BUS 1
B-3
K4-3
K4-2
K4-1
J5-5
A-9
J5-4
J5-3
J5-2
J5-1
A-10
A-14
A-15
(OPT.)
J0-8
J0-7
J0-1
J0-35
J0-47
SET_LAT
K5-7
K5-6
K5-3
K5-5
RESET_LAT
J0-24
K5-1
DALM
K5-4LO_A LM
J0-23
K5-2
J0-46
CC_D RV
INTERFACE
BOARD
INCOM
CONNECTOR
J0-32
J0-33
J0-31
J0-30
J0-10
J0-11
J0-28
J0-27
J0-9
J0-2
MOTOR
ELECTRIC OPERATOR
(OPTIONAL)
AUX. SWITCH
J2-1
J2-2
J2-3
J2-4
J2-5
J2-6
J1-1
J1-2
J1-3
N
Vc
Vb
Va
1
1
10:1
10:1
10:1
ACTC
ACTB
AC TA
ACTN
10:1
BROW N
LINE
LOAD
GF_SGND
ZONE_OUT
ZONE_IN
ZONE_COM
WHITE
(OPT.) OTS1_BREAK
OTS1 _MAKE
A-1
A-2
A-3
OTS1
OTS2
BRNWHT
RED
PT MODULE
+
BLACK
SEE NOTE 1
OTS1 _COM
OTS2 _BRE AK
OTS2 _COM
OTS2 _MAKE
B-19
B-18A-29
A-30
52a
52b
52b
52a
A-28
A-27 B -16
B-17
B-21
B-20 B-2 4
B-25
UVR
UVR
B-29
B-28
B-30
RESERVED FOR
B-23
B-22
B-27
B-26
BLACK
A-24
A-23A- 19
A-20
52b
52a
A-22
A-21 A -25
A-26
AUX. SWITCH
(OPTIONAL)
MOTOR-
MOTOR+
NPOW
A BUS
A BUS
OU TPUT +
OU TPUT -
SR
SR
A-11
INCOM CLOSE
ATR_ LAT CH
ATR_ REL _C OM
ATR_ ALA RM
ATR_ VOLTA GE
ATR_ V_C OM
K1
K4s
K4r
K3
K2
ST
ST
P2-2
52a
P2-1
A-16
(WHEN REQ.)
CC1
CC2
L02 P1
SEE NOTE 3
DIELECTRIC DISCONNECT PLUG
(MOUNTED ON LEFT SIDE OF BREAKER)
J9-3
J9-2
J9-1
J8
J7
J6
P3-3
P3-2
P3-1
P3-6
P3-5
P3-4
H2
X2
X1
CUSTOMER
SEE NOTE 7
SEE NOTE 8
SEE NOTE 6
MOTOR CUT-OFF
SWITCH
LEV-IN
DOOR SWITCH
(WHEN REQ.)
RESISTOR
BRIDGE RECTIFIER
(WHEN REQ.)
(OPT.)
NOTES:
1. 3 WIRE CRIMP IF HIGH INST TRIP MODULE IS SUPPLIED.
2. ALL AUX. SWITCH CONTACTS SHOWN WITH BREAKER IN OPEN POSITION
AND WITH TRIP UNIT IN "NON-TRIPPED" STATE (OTS SWITCHES).
3. THE "SR" DEVICE HAS ADDITIONAL CIRCUITRY THAT PROVIDES A 0.5
SECOND SIGNAL PULSE FOR CLOSING OPERATION. POWER MUST BE
REMOVED AND THEN REAPPLIED FOR A SUBSEQUENT OPERATION.
4. TO PROVIDE SELECTED TIME DELAYS FOR SHORT TIME AND/OR GROUND
TIME FUNCTIONS FOR TESTING OR NON-ZONE INTERLOCKING APPLICATIONS,
A JUMPER FROM B-8 TO B-9 IS REQUIRED.
5. ON THREE POLE BREAKERS ONLY, HAVING GROUND FAULT FUNCTIONALITY,
A JUMPER INSTALLED FROM B-6 TO B-7 WILL ENABLE SOURCE GROUND
FAULT SENSING AND DISABLE RESIDUAL GROUND FAULT SENSING. INPUTS
B-4 AND B-5 WILL BE REASSIGNED FOR SOURCE GROUND SENSOR INPUTS.
6. NORMALLY OPEN CONTACT PROGRAMMED AS RELAY A, VIA DIGITRIP FRONT PANEL.
7. NORMALLY CLOSED CONTACT PROGRAMMED AS RELAY B, VIA DIGITRIP FRONT PANEL.
8. NORMALLY OPEN CONTACT PROGRAMMED AS RELAY C, VIA DIGITRIP FRONT PANEL.
SEE N OTE 9
9
JUMPERING B-3 (NPOW) TO B-7 TERMINAL WILL ELIMINATE REVERSE POWER CONDITION
10. JUMPERING B-6 TO B-7 WILL DEFEAT RESIDUAL GROUND FAULT ELEMENT.
Courtesy of NationalSwitchgear.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton Cutler-Hammer Digitrip 1150+ and is the answer not in the manual?

Eaton Cutler-Hammer Digitrip 1150+ Specifications

General IconGeneral
BrandEaton
ModelCutler-Hammer Digitrip 1150+
CategoryCircuit breakers
LanguageEnglish

Related product manuals