5 Appendix
5.1 Technical Data
Elektronischer Motorstarter EMS/Electronic Motor Starter EMS 04/15 MN03407009Z-DE/EN www.eaton.com 53
5 Appendix
5.1 Technical Data
General Unit EMS-…-2,4-… EMS-…-9-…
Standards IEC/ EN 60947-4-2,
IEC/ EN 61508-1, ISO 13849
IEC/ EN 60947-4-2,
IEC/ EN 61508, ISO 13849
Dimensions (W x H x D)
mm 30 x 157 x 124 30 x 157 x 124
Weight kg 0.3 0.3
Mounting Considerations
Top-hat rail IEC/EN 60715, 35 mm Top-hat rail IEC/EN 60715, 35 mm
Mounting position vertical (mounting rail horizontal) vertical (mounting rail horizontal)
Degree of protection IP20 IP20
lifespan Operations 3 x 10
7
3 x 10
7
Maximum switching frequency (50:50 duty cycle) Operations/h 7200 7200
Electromagnetic compatibility (EMC)
Electrostatic discharge (IEC/EN 61000-4-2)
Air discharge kV 8 8
Contact discharge kV 6 6
Electromagnetic fields (IEC/EN 61000-4-3)
80 - 1000 MHz V/m 10 10
1.4 - 2 GHz V/m 10 10
2 - 2.7 GHz
V/m 3 3
Radio interference suppression
Burst (IEC/EN 61000-4-4) kV 2 2
Surge (IEC/EN 61000-4-5)
Symmetric kV 1 1
asymmetrical
kV 2 2
Radiated RFI (IEC/EN 61000-4-6, Level 3)
V 10 10
Ambient climatic conditions
Operating ambient temperature °C -25 - +60 -25 - +60 (Derating)
Condensation not permissible, prevent with
suitable measures
not permissible, prevent with
suitable measures
Storage
°C -40 - +80 -40 - +80
Relative humidity, no condensation (IEC/EN 60068-2-30)
Input data
Rated control voltage U
s
(EN 60947-1) V DC 24 24
Control voltage V DC 24 (-20 % +25 %) 24 (-20 % +25 %)
Residual ripple % 5 5
Rated control supply current I
s
(EN 60947-1)
(without feedback)
mA 40 40
Rated control circuit voltage
V DC 24 24