Figure 1. Substation mounting dimensions for NOVA recloser, DAS switch, VCS-3 switch, and TVS sectionalizer.
2216
(87.25)
adjustable to
2826
(111.25)
in
76 (3)
increments
1060
(41.75)
965
(38)
457
(18)
552
(21.75)
19 (0.75)
Mounting Hole (4)
B
O
P
E
N
C
A
Step 1
Items 9, 13,
and 14
Step 1
Items 9, 13,
and 14
Installation dimensions
ote:N All dimensions are mm (inches). Dimensions shown are approximate.
UNIT TYPE Rating
A
(at minimum height) B C
NOVA Recloser 15 kV (110 kV BIL) 3124 (123) 908 (35.75) 508 (20)
15 kV (125 kV BIL) 3180 (125.25) 964 (38) 564 (22.25)
27 kV (125 kV BIL) 3180 (125.25) 964 (38) 564 (22.25)
27 kV (150 kV BIL) 3279 (129) 1063 (41.75) 663 (26)
38 kV 3279 (129) 1063 (41.75) 663 (26)
DAS Switch
without CT
15 kV 3067 (120.75) 851 (33.5) 508 (20)
27 kV 3128 (123.25) 911 (36) 569 (22.5)
DAS Switch
with CT
15 kV (110 kV BIL) 3124 (123) 908 (35.75) 508 (20)
15 kV (125 kV BIL) 3180 (125.25) 964 (38) 564 (22.25)
27 kV (125 kV BIL) 3180 (125.25) 964 (38) 564 (22.25)
27 kV (150 kV BIL) 3279 (129) 1063 (41.75) 663 (26)
38 kV 3279 (129) 1063 (41.75) 663 (26)
VCS-3 Switch 15 kV 3067 (120.75) 851 (33.5) 508 (20)
27 kV 3128 (123.25) 911 (36) 569 (22.5)
2 SUBSTATION FRAME KNOVA59-1 AND KNOVA59-3 ASSEMBLY AND INSTALLATION INSTRUCTIONS MN280043EN January 2016

Other manuals for Eaton KA146W5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton KA146W5 and is the answer not in the manual?

Eaton KA146W5 Specifications

General IconGeneral
BrandEaton
ModelKA146W5
CategoryCables and connectors
LanguageEnglish

Related product manuals