EQUIPMENT AND OPTIONAL ACCESSORIES - WHAT THEY DO
SERVICE HINTS
You may avoid inconvenience and service calls by checking these points before you call for service.
!
CAUTION
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do
not use any phone in your building.
Immediately call your gas supplier
from a neighbor’s phone. Follow gas
supplier’s instructions.
If you cannot reach your gas supplier,
call the re department.
Possible Cause What to do
Thermostat is not set correctly Reset thermostat above room temperature
Burner is not operating properly Check ame. If it is yellow, the burner is not getting enough air.
Or, if ame is blue and noisy and seems to lift off the burner, the
burner is getting too mush air. Contact your service technician.
No electric power to boiler Check over current protection. Check to be sure electric power
supply circuit is “ON”.
Controls out of adjustment Reset according to instructions.
Radiators not heating Open radiator vents to excess air. Check ow control valve (if
used). It may be in closed position.
Circulating pump not running Check over current protection. Check relay operation.
Poor electrical contact Check all control terminals and wire joints.
Rollout switch blown Have your service technician check heat exchanged for blockage.
Replace rollout switch with exact replacement.
Spill switch blown Have your service technician check venting system and chimney
for blockage, or down draft condition. Reset spill switch.
Vent damper not operating Consult troubleshooting guide in Ef kal manual, packaged with
vent damper.
Possible Cause What to do
Gas input amount is incorrect Contact your service technician.
Possible Cause What to do
Dirt on seat Open valve manually. Allow water to run and clear valve seat.
Water logged expansion tank Drain tank, see instructions.
IF YOUR SYSTEM IS NOT HEATING OR NOT GIVING ENOUGH HEAT . . .
IF BURNER IS NOISY . . .
RELIEF VALVE LEAKING . . .
HAVE YOUR SERVICE TECHNICIAN CHECK ANY PROBLEM YOU ARE UNABLE TO CORRECT.