Section 7: XTE3000 – RDM Functional Table
XTE3000 – RDM Functional Table
Section 7: XTE3000 – RDM Functional Table
XTE3000 could be controlled by multiple different control sources, RDM (Remote Display
Module), Bus (Modbus, Hart and etc.), 4 to 20 mA Analog, Discrete Hardwire and Local Display
Control. Table 1 shows the priority of combination of each control methods.
Table 1.
Restricted
Param.
“Positioner
Request From”
Actuator
Local Selector
Position
HW Remote Mode
(Terminal C8)
RDM Selector
Position
DCS
Communication
Status
4 to
20 mA
control
enabled
Actuator executes
commands received by
Bus LOCAL - - - - LOCAL CONTROL PANEL
Bus OFF - - - - No commands executed
Bus REMOTE ENERGIZED - - -
HW REMOTE
(Terminals C5, C6, C7)
Bus REMOTE NOT ENERGIZED LOCAL - - RDM
Bus REMOTE NOT ENERGIZED OFF - - No commands executed
Bus REMOTE NOT ENERGIZED REMOTE/ERROR ACTIVE - DCS
Bus REMOTE NOT ENERGIZED REMOTE/ERROR NOT ACTIVE - No commands executed
4 to 20 mA LOCAL - - - - LOCAL CONTROL PANEL
4 to 20 mA OFF - - - - No commands executed
4 to 20 mA REMOTE ENERGIZED - - -
HW REMOTE
(Terminals C5, C6, C7)
4 to 20 mA REMOTE NOT ENERGIZED LOCAL - - RDM
4 to 20 mA REMOTE NOT ENERGIZED OFF - NO No commands executed
4 to 20 mA REMOTE NOT ENERGIZED REMOTE/ERROR - ENABLED
The 4 to 20 mA has the
control of the actuator