33
Installation
Modbus Communications
The drive’s serial communication protocol is Modbus RTU slave with a 32 bit data extension.
The Modbus protocol is available on most operator interface panels and PLC’s.
Control Techniques’ Motion Interface panels are supplied with a Modbus master
communications driver.
Multi-Drop Communications
The RS-485 option (pins 4 and 9) is provided for multi-drop configurations of up to 32 drives.
Control Techniques provides a special multi-drop serial cable which allows you to easily
connect two or more drives.
Figure 32: EN Multi-Drop Wiring Diagram
Serial Communications Specifications
Max baud rate 19.2k
Start bit 1
Stop bit 2
Parity none
Data 8
Note:
The terminating resistor packs, TERM-H
and TERM-T, should be installed on the
first (TERM-H) and last (TERM-T) drive in
the string if the total cable length is over
50 feet.
TIA-XXX
Serial Cable
TERM-H
TERM-T
DDS-XXX
Serial Cables
DDS-XXX
Serial Cables
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Other manuals for Emerson Control Techniques EN Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Control Techniques EN Series and is the answer not in the manual?

Emerson Control Techniques EN Series Specifications

General IconGeneral
BrandEmerson
ModelControl Techniques EN Series
CategoryDC Drives
LanguageEnglish

Related product manuals