© 2016 Emerson Climate Technologies, Inc.
AE4-1303 R15
Figure 3
Compressor Terminal Box Wiring with CoreSense Protection
2
3
1
4
4
2
1 2 3 4 5 6 7 8 9 10
T2 T1
L3
L2L1
M2
M1
WARNING: GREEN FLASHING + PAUSE 2 SEC. /
PRECAUCION: LUZ VERDE CENTELLEANTE + PAUSA 2 SEG
TRIP: RED FLASHING + PAUSE 2 SEC. /
INTERRUPCION DE FUNCION = LUZ ROJA CENTELLEANTE + PAUSA 2 SEG
LOCKOUT: RED FLASHING + PAUSE 2 SEC. + SOLID 3 SEC. + PAUSE 2 SEC. /
PERDIDA DE FUNCION: LUZ ROJA CENTELLEANTE + PAUSA 2 SEG + LUZ
SOLIDA 3 SEG + PAUSA 3 SEG
ALERT CODE (RED)
/ CODIGO DE ALERTA (ROJO)
TYPE / TIPO
EVENT / EVENTO
SOLID / SOLIDO
LOCKOUT /
PERDIDA DE FUNCION
LOSS OF FUNCTION /
PERDIDA DE FUNCION
1
TRIP /
INTERRUPCION DE FUNCION
MOTOR HIGH TEMPERATURE /
TEMPERATURA DE MOTOR ELEVADA
2
LOCKOUT/TRIP /
PERDIDA DE FUNCION /
INTERRUPCION DE FUNCION
N/A
3
LOCKOUT /
PERDIDA DE FUNCION
MISSING PHASE / FASE FALTANTE
4
N/A
REVERSE PHASE / FASE AL REVES
5
OPEN / SHORT MOTOR THERMISTOR /
TERMISTOR DEL MOTOR EN CIRTUITO
ABIERTO O CORTOCIRCUITO
6
N/A
FUTURE USE / USO FUTURO
7
MODULE LOW VOLTAGE /
BAJO VOLTAJE AL MODULO
9
TRIP /
INTERRUPCION DE FUNCION
SHORT CYCLING /
CICLO FRECUENTE
WARNING (GREEN) /
PRECAUCION (VERDE)
TYPE / TIPO
EVENT / EVENTO
SOLID / SOLIDO
NORMAL /
NORMAL
NORMAL OPERATION /
OPERACION NORMAL
1
WARNING /
PRECAUCION
2
FUTURE USE / USO FUTURO
3
LOSS OF COMMUNICATION /
PERDIDA DE COMUNICACIONES
DIP SWITCH /
DIP SWITCH
PURPOSE / PROPOSITO
ON = 1 /
PRENDIDO = 1
OFF = 0 /
APAGADO = 0
1 -LSB
0
UNIQUE ADDRESS / DIRECCION UNICA
RANGE 1 TO 32 / RANGO DESDE 1 HASTA 32
(EXAMPLE = 12) / (EJEMPLO = 12)
2
3
4
5 - MSB
6
7
8
9
10
0
TEMP. CONNECTOR CONFIGURATION /
CONFIGURACION DEL CONECTOR DE SENSOR DE TEMPERATURA
BAUD RATE / BAUD RATE
PARITY / PARIDAD
COMMUNICATION / COMUNICACION
SHORT CYCLE PROTECTION /
PROTECCION CONTRA CICLADO FRECUENTE
1
1
0
9,600
19,200
EVEN / PAR
STANDALONE /
DESCONECTADO DE LA RED
ENABLE /
ACTIVADO
DISABLE /
DESACTIVADO
0
NONE / NINGUNA
LOCKOUT /
PERDIDA DE FUNCION
WARNING /
PRECAUCION
WARNING /
PRECAUCION
NETWORK /
CONECTADO A LA RED
LOCKOUT/TRIP /
PERDIDA DE FUNCION /
INTERRUPCION DE FUNCION
4
N/A
N/A
5
WARNING /
PRECAUCION
FUTURE USE / USO FUTURO
SHORT CYCLING /
CICLO FRECUENTE
8
N/A
FUTURE USE / USO FUTURO
SYMBOLS / SIMBOLOS
MOTOR WINDINGS
CONNECTIONS / CONEXION
DE DEVANADO DEL MOTOR
L1
L2
L3
JUMPER / JUMPER
COMMUNICATION PORT /
PUERTO DE COMUNICACION
PROTECTOR MODULE VOLTAGE / VOLTAGE DEL MODULO DE PROTECCION
DIP SWITCHES /
DIP SWITCHES
LED’S / LED’S
TEMP SENSORS /
SENSORES DE TEMPERATURA
USE COPPER CONDUCTORS ONLY.
USE MINIMUM 75º C WIRE FOR AMPACITY DETERMINATION.
USE THIS EQUIPMENT ON A GROUNDED SYSTEM ONLY.
PRIMARY SINGLE PHASE FAILURE PROTECTION IS PROVIDED.
PROTECTOR MODULE AND OPTIONAL CRANKCASE HEATER MUST
BE CONNECTED ONLY TO THEIR RATED VOLTAGE.
OVERCURRENT PROTECTION DEVICE RATING AND TYPE MUST
BE IN ACCORDANCE WITH REGULATORY AGENCY END PRODUCT APPROVALS
- SEE SYSTEM NAMEPLATE.
UTILICE CONDUCTORES DE COBRE UNICAMENTE.
PARA DETERMINAR LA AMPACIDAD DEL CABLE ESCOJA CABLE DE 75ºF.
UTILICE ESTE DISPOSITIVO UNICAMENTE EN SISTEMAS CONECTADOS A TIERRA.
LA PROTECCION DE FALLA DE FASE PRIMARIA MONOFASICA SE PROVEE EN ESTE
DISPOSITIVO. EL MODULO DE PROTECCION Y EL CALENTADOR DE CARTER OPCIONAL
DEBERAN SER CONECTADOS UNICAMENTE A SU VOLTAJE NOMINAL RESPECTIVO.
EL TIPO Y
LAS CARACTERISTICAS NOMINALES DE LA PROTECCION DE SOBRECORRIENTE
DEBEN REPSETAR LAS ESPECIFICACIONES DE LAS AGENCIAS DE CERTIFICACION DEL
EQUIPO
– VER PLACA DE IDENTIFICACION 09-13 052-2841-00
1
4
3
3
L1: RED / ROJO
L2: BLACK / NEGRO
L3: WHITE / BLANCO
TO CONTROL CIRCUIT / PARA CONTROLAR EL CIRCUITO
THERMAL SENSORS DO NOT SHORT / SENSORES DE TEMPERATURA – NO CONECTAR
EN CORTO CIRCUITO
PHASE SENSING / SENSOR DE FASES
L1
L2
L3