STEP 1: Configuring M400 VFD Drive
Note: Do not connect the device communications to E2 controller.
1. Press right/ left arrow key and go to Pr MM.000 then press . Select Reset 60Hz defs then press
.
Note: Pressing allows you to enter and exit parameter edit mode.
2. Press to return the drive into the No Action display.
3. Go to Pr 00.005 (Drive Config), then press . Select Preset, then press .
4. Set Pr 00.010 (User Security Status), then press . Select All Menus, then press .
5. Set Pr 06.004 (Start/Stop Logic), then press . Select 6, then press .
6. Set Pr 11.023 (Serial Address), then press . Select 2, then press .
7. Set Pr 11.024 (Serial Mode), then press . Select 8 1 NP, then press .
8. Set Pr 11.020 (Serial Reset), then press . Select On to reset communications.
Note: The device will flash to On and returns to Off, press .
9. Set Pr 12.000 (Parameter mm.000), then press . Select Save Parameters, then press .
10.Press to return the drive into the No Action display.
Note: The drive is now ready to communicate with the E2 controller and ready for test/run.
Keypad Number Keypad Description
1 (Enter)
The Enter button is used to enter parameter view or edit mode, or to accept a
parameter edit.
2 (Navigation)
The Navigation keys can be used to select individual parameters or to edit parameter
values. In keypad mode, the “Up” and “Down” keys are also
used to increase or decrease the motor speed.
3 (Start) The Start key is used to start the drive in keypad mode.
4 (Stop/Reset)
The Stop / Reset key is used to stop and reset the drive in keypad mode. It can also be
used to reset the drive in terminal mode.
5 (Escape)
The Escape key is used to exit from the parameter edit / view mode or disregard a
parameter edit.