Operating instructions
EXD-SH1/2 Controller with ModBus communication
capability for electrical control valves
Emerson Climate Technologies GmbH www.climate.emerson.com/en-gb Date: 29.07.2020
Am Borsigturm 31 I 13507 Berlin I Germany EXD-SH12_OI_EN_DE_FR_IT_PL_RU_0720_R04_865917.docx
List of parameters in scrolling sequence by pressing
button:
Code Parameter description and choices Min Max
-C2
Circuit 2 of EXD-SH2 enabled
-uC
0 = °C, K, bar 1 = F, psig
1Fct
0 = Superheat control 1 = Temperature control normal sense
2 = temperature control reverse sense
1u4
0 = standard 1 = slow
2 = intermediate control 3 = adjustable fixed PID
1u0
0 = R22 1 = R134a 2 = R507 3 = R404A
4 = R407C 5 = R410A 6 = R124 7 = R744
8 = R407A 9 = R407F 10 = R23 11 = R32*
12 = R1234ze* 13 = R448A 14 = R449A 15 = R450A
16 = R513A 17 = R290* 18 = R1270* 19 = R454C*
1uP
0 = PT5N-07x 1 = PT5N-18x 2 = PT5N-30x
3 = PT5N-50x 4 = PT5N-150D 5 = PT5N-10P-FLR
6 = Ratio metric (gauge) 7 = Ratio metric (absolute) 8 = Modbus
1ut
0 = EX4-6(FLR) 1 = EX7(FLR) 2 = EX8 3 = N/A 4 = N/A
5 = N/A 6 = N/A 7 = N/A 8 = N/A 9 = N/A
10 = CV4 11 = CV5-6 12 = CV7
Start opening duration (s)
1uL
0 = disabled 1 = enabled auto reset 2 = enabled manual reset
Alarm at 0.5K (if it maintains 1 min.); Alarm clear immediately at 3K
1u5
Range = 3-30 K if parameter 1uL is set to 1 or 2
1u2
1u3
Factory setting according to selected refrigerant
(1u0). The default value can be changed
- -
MOP
1P9
0 = disabled 1 = enabled auto-reset 2 = enabled manual reset
Low pressure alarm cut-out (bar)
Low pressure alarm delay (s)
Low pressure alarm cut-in (bar)
1P4
0 = disabled 1 = enabled auto-reset 2 = enabled manual reset
Freeze alarm cut-out (°C)
Superheat control circuit1 (Kp factor)
Display 1/10K
Superheat control circuit1 (Ti factor)
Superheat control circuit1 (Td factor)
Display 1/10K
1uH
High superheat alarm mode
0 = disabled 1 = enabled auto-reset;
High superheat alarm set point (K)
High superheat alarm delay (min)
Temperature control set point (°C)
1tAF
Min. temperature alarm set point (°C)
Min. temperature alarm delay (min)
Max. temperature alarm set point (°C)
Max. temperature alarm delay (min)
1tt
0 = ECN-Nxx (-45…+40°C) / TP1-…(-45…+150°C)
1 = ECN-Z... ( -80…-40°C) for R23
Code Parameter description and choices Min Max
Circuit 2 Parameters (only EXD-SH2)
2u4
0 = standard 1 = slow
2 = intermediate control 3 = adjustable fixed PID
2u0
0 = R22 1 = R134a 2 = R507 3 = R404A
4 = R407C 5 = R410A 6 = R124 7 = R744
8 = R407A 9 = R407F 10 = R23 11 = R32*
12 = R1234ze* 13 = R448A 14 = R449A 15 = R450A
16 = R513A 17 = R290* 18 = R1270* 19 = R454C*
2uP
0 = PT5N-07x 1 = PT5N-18x 2 = PT5N-30x
3 = PT5N-50x 4 = PT5N-150D 5 = PT5N-10-FLR
6 = Ratio metric (gauge) 7 = Ratio metric (absolute)
8 = Modbus 9 = Pressure sensor circuit1 is used (1uP)
2ut
0 = EX4-6(FLR) 1 = EX7(FLR) 2 = EX8 3 = N/A 4 = N/A
5 = N/A 6 = N/A 7 = N/A 8 = N/A 9 = N/A
10 = CV4 11 = CV5-6 12 = CV7
Start opening duration (s)
2uL
0 = disabled 1 = enabled auto reset 2 = enabled manual reset
Alarm at 0.5K (if it maintains 1 min.); Alarm clear immediately at 3K
2u5
Range = 3-30K if parameter 2uL is set to 1 or 2
2u2
2u3
Factory setting according to selected refrigerant
(2u0). The default value can be changed
- -
MOP
2P9
0 = disabled 1 = enabled auto-reset 2 = enabled manual reset
Low pressure alarm cut-out (bar)
Low pressure alarm delay (s)
Low pressure alarm cut-in (bar)
2P4
0 = disabled 1 = enabled auto-reset 2 = enabled manual reset
Freeze alarm cut-out (°C)
Superheat control circuit2
(Kp factor), fixed PID Display 1/10K
Superheat control circuit2 (Ti factor),
fixed PID
Superheat control circuit2
(Td factor), fixed PID Display 1/10K
2uH
High superheat alarm mode
0 = disabled 1 = enabled auto-reset;
High superheat alarm set point (K)
High superheat alarm delay (min)
2tt
0 = ECN-Nxx (-45…+40°C) / TP1-…(-45…+150°C)
1 = ECN-Z60 ( -80°C…-40°C) for R23
*) Warning -Flammable refrigerants:
EXD-SH1/2 (EXD-PM, ECP-024) has a potential ignition source and does not
comply with ATEX requirements. Installation only in non-explosive
environment. For flammable refrigerants only use valves and accessories
approved for it!
MOP default value table: