Liebert GXTMT Series Installation and User Manual
1-3 kVA UPS
Page 21 V2.11 Emerson Network Power
11. Technical Data
Module W×H×D (mm) Weight (kg)
Power module GXT1000-MT 145X220X400 14
Power module GXT1000L-MT 145X220X400 7
Power module GXT2000-MT 192X347X460 34.5
Power module GXT2000L-MT 192X347X460 15
Power module GXT3000-MT 192X347X460 35.5
Power module GXT3000L-MT 192X347X460 16
EMS
Item Standard Level
ESD immunity IEC61000-4-2
Level 4
RS immunity IEC61000-4-3 Level 3
EFTB immunity IEC61000-4-4 Level 4
Surge immunity IEC61000-4-5 Level 4
Item (for GXTL models) Standard Level
Limitation of emission of input harmonic currents EN61000-3-2 -
Limitation of voltage changes, voltage fluctuations and flicker EN61000-3-3 -
Conducted Emission EN50091-2 Class B
Radiated Emission
EN50091-2 Class B
Environmental
Item
Ambient temperature
Relative humidity
Altitude
Storage temperature
-0°C~40°C (excluding battery)
Mechanical
EMI
Lower than 1000m; no derating;
1000~1500m; 1% derating for every 100m rise
Less than 90% Condensing
0°C~40°C
Normal range
Technical Data