1A 4A 1A 8A 1A 8A
Qty. ×Volts. ×Capacity
3×12V×7.2Ah -
8X12X7.2Ah
-
8X12X7.2Ah
-
Manufacturer / model
CSB/GP1272F2
or Panasonic
equivalent
-
CSB/GP1272F2
or Panasonic
equivalent
-
CSB/HRL1234W
F2 or Panasonic
equivalent
-
Typical Autonomy Time
12 Minutes
-
15 Minutes
-
9 Minutes
-
Autonomy at Half Load
20 Minutes
-
26 Minutes
-
16 Minutes
-
Charging duration
Model
Electrical
Normal mode: ≥88% (rated mains voltage, full linear load, battery fully charged)
IP20(static state) Protection
Rating
Charging current
80~264V
Normal<
-
>Battery: 0ms
≤200mV
GXT1000L-MT, GXT2000L-MT, GXT3000L-MT: <45db
External battery voltage 36Vdc 96Vdc
Noise (within 1m)
Battery
0.97 (conditions: rated voltage, full pure resistive load, fully charged battery)
1-phase, plus PE
0.7
50 / 60 Hz ±0.2Hz
1000VA/700W 2000VA/1400W 3000VA/2100W
1-phase, plus PE
80% of battery capacity in 4 hrs (standard type)
>150% 300ms
300% for 5s
220Vac / 230 Vac / 240 Vac ±2%
≤2%(0~100% linear load)
≤6%(0 ~100% non-linear load)
<5% in 20 ms
46-54 Hz / 56-64 Hz
>150% 300ms
3:1
Input
Output
≤3%(0 ~100% linear load)
Inverter overload capability (in
Normal mode, 25°C)
108%~150% 30s
Inverter overload capability (in
Battery mode, 25°C)
108%~150% 30s
220Vac / 230Vac / 240 Vac
1. 160~300 Vac full load 2. 110 Vac half load
50/60 Hz
Bypass overload capability
200% for < 60 mins
Battery mode: ≥83% (rated battery voltage, full linear load)
Voltage harmonic distortion
(rated input voltage, rated input
frequency)
Units with CE markings comply with the following standards:
1) For
GXT1000L-MT/ GXT1000L-MT / GXT1000L-MT
EN62040-1-1 (safety)
Conducted Emission: EN50091-2 ...................................................................Class B
Radiated Emission: EN50091-2 ......................................................................Class B
Harmonic Current: EN61000-3-2
Voltage Fluctuations and Flicker: EN61000-3-3
EMS: EN61000-4-2(ESD) ............................................................................... Level 4
EN61000-4-3(RS) .......................................................................................... Level 3
EN61000-4-4(EFT).......................................................................................... Level 4
EN61000-4-5(lighting surge) ........................................................................... Level 4
EN61000-2-2 (Immunity to low frequency signals)