MAS2600: Ordering Information Reference Manual
August 2023 RM 6000-01-001-24
17
Cable
MAS 2600 -XXX-XX-X/XX
Two types of transducer cables are available. The standard cable for applications with tem-
peratures up to 80C, and high temperature cable for applications with temperatures up to
125C. The transducer cable is delivered in whole meters.
To make the MAS 2600 transmitter easy to install, and for later service purposes, the trans-
ducer cable should be as short as possible, though considering the position of the trans-
ducer and amplifier box.
Note! Maximum cable length:
Safe area
Standard cable 300 m
High temperature cable 300 m
Hazardous area
Standard cable 44 m
High temperature cable 34 m