12 Technical data
12.1 Drive technical data
12.1.1 Power and current ratings
The power ratings for the 480V, 575V and 690V configurations are
shown in Table 12-1, Table 12-2 and Table 12-3.
The continuous current ratings given are for a maximum ambient
temperature of 40°C and an altitude of 1000m. For operation at higher
temperatures and altitudes derating is required.
The maximum continuous output current rating of the drive should be
‘derated’ for operation at altitudes above 1000m. The derating is to be
1% derating of rated output current per 100m above 1000m to a
maximum derating of 20% at 3000m.
Table 12-1 480V current ratings
Table 12-2 575V current ratings
* For this rating at 575V, 150% overload time is 20s at 40°C and 30s at
35°C
Table 12-3 690V current ratings
* For this rating at 690V, 150% overload time is 20s at 40°C and 30s at
35°C
Maximum continuous input current
The values of maximum continuous input current are given to aid the
selection of cables and fuses. These values are stated for worst-case
conditions.
For current ratings above 1850A then parallel connection of the drives is
required. However, this function is not implemented on firmware
versions V01.05.00 and earlier.
12.1.2 Typical short-term overload limits
The maximum percentage overload limit changes depending on the
selected motor
Variations in motor rated current will result in changes in the maximum
possible overload as detailed in the Mentor MP Advanced User Guide.
Figure 12-1 can be used to determine the maximum overload duration
available for overloads between 100% and 150%. For example the
maximum overload available for a period of 60 seconds is 124%.
Figure 12-1 Maximum overload duration available
Overload of 150% for 30s is available up to a maximum of 10 repetitions
per hour.
Model
AC input
current
DC output current
Typical motor
power
Continuous Continuous
150%
overload
@
400Vdc
@
500Vdc
AAAkWhp
MP25A4(R) 22 25 37.5 9 15
MP45A4(R) 40 45 67.5 15 27
MP75A4(R) 67 75 112.5 27 45
MP105A4(R) 94 105 157.5 37.5 60
MP155A4(R) 139 155 232.5 56 90
MP210A4(R) 188 210 315 75 125
MP350A4(R) 313 350 525 125 200
MP420A4(R) 376 420 630 150 250
MP550A4(R) 492 550 825 200 300
MP700A4(R) 626 700 1050 250 400
MP825A4(R) 738 825 1237.5 300 500
MP900A4(R) 805 900 1350 340 550
MP1200A4(R) 1073 1200 1800 450 750
MP1850A4(R) 1655 1850 2775 700 1150
Model
AC input
current
DC output current
Typical motor
power
(With Vdc =
630V)
Continuous Continuous
150%
overload
AAAkWhp
MP25A5(R) 22 25 37.5 14 18
MP45A5(R) 40 45 67.5 25 33
MP75A5(R) 67 75 112.5 42 56
MP105A5(R) 94 105 157.5 58 78
MP155A5(R) 139 155 232.5 88 115
MP210A5(R) 188 210 315 120 160
MP350A5(R) 313 350 525 195 260
MP470A5(R) 420 470* 705 265 355
MP700A5(R) 626 700 1050 395 530
MP825A5(R) 738 825* 1237.5 465 620
MP1200A5(R) 1073 1200 1800 680 910
MP1850A5(R) 1655 1850 2775 1045 1400
Model
AC input
current
DC output Current
Typical motor
power (With
Vdc = 760V)
Continuous Continuous
150%
Overload
AA*AkWhp
MP350A6(R) 313 350 525 240 320
MP470A6(R) 420 470* 705 320 425
MP700A6(R) 626 700 1050 480 640
MP825A6(R) 738 825* 1237.5 650 850
MP1200A6(R) 1073 1200 1800 850 1150
MP1850A6(R) 1655 1850 2775 1300 1750
100
105
110
115
120
125
130
135
140
145
150
155
160
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
200
overload duration (seconds)
overload
(%)