Quick Start Guide Section 3
GFK-2893P Sep 2019
Initial Startup 13
3. Initial Startup
Note: For installation requirements, complete installation
procedures, and operating information, refer to the
QuickPanel+ Operator Interface User Manual (GFK-
2847).
You will need the following:
▪ A Safety Extra Low Voltage (SELV) and Limited
Energy Circuit or SELV and Class 2 dc power supply.
▪ The power terminal block is supplied with the
product. For voltage and requirements, refer to the
Input Power specifications in the table, General
Specifications.
▪ The mating power terminal block supports
stranded 30 to 14 AWG (0.05 to 2.00 mm
2
) wires.
The user calculates proper gauge wiring for current
carrying capacity and loss according to local
regulations.
▪ At a minimum, the cable must be rated for 75°C
(167 °F) or more.
ELECTRICAL SHOCK HAZARD - To avoid personal injury or
damage to equipment, ensure that the dc supply is
disconnected from power and the leads are not energized
before attaching them to the unit's power supply plug.