A G-TRAC2
IOM-25 19 of 42 Mar 99 R7
as per both the setting of pot 5 and the discharge set point. The calculated discharge air set point (dial setting + reset) is
limited between 48°F and 120ºF.
To determine the amount of reset available use the following chart (See page 21).
EXAMPLE: G-TRAC2 set point 70°F
Reset Ratio Pot set at 3 (total reset 29°: +18 is upper reset limit, -11 is lower reset limit)
Room thermostat set at 72°F
Discharge set point is 65°
If actual room temperature sensor is at 72ºF (satisfied), there is no reset. The unit discharges at 70ºF.
If room gradually cools so sensor is 3º colder (67ºF), discharge temperature resets up the full amount of its authority
(+18) to 88ºF.
If room only cooled to 70ºF (2 degrees) the new discharge temperature would be * 18 = 12°. Therefore 12° + 65ºF
set point = 77º discharge.
If the room had warmed above the temperature of the room thermostat, a similar reset action would occur except the
discharge temperature would be reduced.
Discharge Operating Range
Absolute lowest
allowed discharge set
point
Absolute highest
allowed discharge
set point
Same as Diagram A but demonstrates reset moves Up and Down with Manual Set Point.
Manual Set Point has been turned to 80° in this example.
Discharge Operating Range
Absolute lowest
allowed discharge set
point
Absolute highest
allowed discharge
set point