A G-TRAC2
IOM-25 32 of 42 Mar 99 R7
XXII. G-TRAC2 SET UP SHEET
Rev. OCT/08
Job #_________Tag #__________Designer________Model #______________Date_________
BASE SETPOINT LOCATION G-TRAC2 ________ or Remote ________
Base discharge set point *_____________ degrees F
*Set point is not required when GTrac-2 is DIRECT controlled by other controllers.
ROOM RESET [YES] __________ [NO] ___________
(dipswitch A-3)
Reset Ratio Pot Setting _______________________________
NOTE: The room reset is bi-directional.
AMBIENT RESET [YES] __________ [NO] ___________
(dipswitch A-2)
Reset Ratio Pot Position _______________________________
NOTE: Ambient reset is bi-directional. The ambient temperature range through which the discharge
temperature is reset is -15 to 70°F.
BMS VOLTAGE or CURRENT RESET [YES] __________ [NO]____________
(dipswitch A-1)
Reset Amount (specify amount 15°F(8.3°C) to 60°F(33.3°C) _________ degrees F
NOTE: Voltage/Current reset is in the up direction only.
GTRAC-2 DIP SWITCH BLOCK “C” SETTING
Non-Direct Control Direct Control (GTRAC-2 Slaved to other controllers)
(Including BMS Reset)
Stand Alone______ or BMS or Metasys______ or CTRAC3______
(C2 “on” only) ( C1, C3 & C4 ”on”only) (C3 & C4 “on” only)
AUTO BYPASS LOW LIMIT
(dipswitch C-5)
OPERATIONAL ON _________ DISABLED OFF __________
BLOWER OPERATION
(dipswitch A-4)
Air Priority** “ON” ________ Temperature Priority “OFF” _______
**Air priority feature can not be used in cold weather with make up air function, unit will start supply fan before dampers
open. If this option is needed size damper motor adequately or put 40seconds TDR on supply fan to allow dampers to open
past 45% before supply fan to starts.
NIGHT OPERATION [YES] __________ [NO]____________
(Terminal K is powered)