Eubank EAA/EGA Wall Mount AC Installation & Operation Manual
03/2021 Rev.5
35
Additional Items Needed:
Additional hardware and miscellaneous supplies (not furnished by Eubank
®
) are needed for installation.
For example, the list below contains approximate quantities of items typically needed for mounting
a unit on a wood frame wall structure. Concrete or berglass structures have different requirements.
(10) 3/8" carriage head mounting bolts for unit mounting anges. The length needed is typically
the wall thickness plus one inch.
(20) 3/8" washers
(10) 3/8" hex nuts
(6) 3/8" x 2-1/2" lag screws for bottom bracket
Silicone Sealer to seal around cracks and openings
Minimum 5 conductor low voltage multicolored wire cable (i.e. thermostat wire)
Appropriate electrical supplies such as conduit, electrical boxes, ttings, wire connectors,
etc.
High voltage wire, sized to handle the MCA (minimum circuit ampacity) listed on the data
plate.
Over-Current Protection Device sized in accordance with the MFS (maximum fuse size) listed
on the unit data plate.
WARNING - FIRE HAZARD
Improper adjustment, alteration, service, maintenance or installation could cause serious
injury, death and/or property damage.
Installation or repairs made by unqualied persons could result in hazards to you and
others. Installation MUST conform with local codes or, in the absence of local codes, with
codes of all governmental authorities have jurisdiction.
The information contained in this manual is intended for use by a qualied service
agency that is experienced in such work, is familiar with all precautions and safety
procedures required in such work, and is equipped with the proper tools and test
instruments.
3.4 Porting and Duct Work
General Information
Note: The following instructions are for general guidance only. Due to the wide variety of installation
possibilities, specic instructions will not be given. When in doubt, follow standard and accepted
installation practices, or contact Technical Support for additional assistance.
Wall Openings (All EAA and EGA air conditioners)
Measure the dimensions of the supply and return ports on the unit.
Cut the openings in the exterior wall for the supply and return. IMPORTANT: All units with electric
heat must have 1" (25.4mm) clearance on all four sides of the supply outlet duct ange on the
unit. The 1" (25.4mm) clearance must extend on all sides of the supply duct for the rst 3 feet (1
meter) from the unit.
IMPORTANT: Eubank
®
requires a minimum of 1" (25.4mm) from the surface of any supply ducts
to combustible material for the rst 3 feet (1 meter) of the duct.
For all air conditioners with electric heat, the wall sleeve MUST have 1” (25.4 mm) clearance around
all four sides of the opening. Attach the perimeter ange of the wall sleeve to the framed opening with
appropriately sized screws. Since electric heat can be added after the unit has been installed, Eubank
recommends that all installations have the 1” (25.4 mm) clearance around the wall sleeve.
When installing the wall sleeve, the supply opening must be on top. The supply opening is smaller than
the return air opening.