EasyManuals Logo
Home>Fisher>Controller>FIELDVUE DVC6200

Fisher FIELDVUE DVC6200 Instruction Manual Supplement

Fisher FIELDVUE DVC6200
5 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
www.Fisher.com
Zero Point Calibration
HART
®
Communicating Fisher
FIELDVUE
DVC6200 Digital Valve Controllers
The Zero Point Calibration procedure allows you replace an existing DVC6200 digital valve controller without
performing a travel calibration. This procedure can be used when a situation occurs that requires the partial or
complete replacement of a digital valve controller when part of a valve assembly that does not have a process bypass
or the process cannot be shut down.
WARNING
Personal injury or property damage, caused by unexpected valve movement and an uncontrolled process, could result if
this procedure is attempted when the valve is not locked at its present position. If you cannot safely lock the valve in
position until this procedure is complete, do not proceed with this procedure.
Notes
This procedure should only used for the partial or complete replacement of a digital valve controller when the valve does not have
a bypass or the process cannot be shut down. Do not proceed with this procedure if the valve has a bypass or the process can be
shut down.
This procedure assumes the array was set up properly on the existing DVC6200 and has not been moved or adjusted since setup.
The valve will need to be locked at its present position. This can be accomplished by using a handwheel or other mechanism. If you
cannot safely lock the valve in position until this procedure is complete, do not proceed with this procedure.
This procedure requires the use of a 475 Field Communicator, AMS Trex
Device Communicator, or ValveLink
software.
This procedure can be used to swap a DVC6200 with another DVC6200. You cannot swap a DVC6000 with a DVC6200 using this
procedure. The DVC6200 used to replace the existing digital valve controller must be a new, factory calibrated instrument. This
procedure will not work if a previously installed and calibrated digital valve controller is used.
Zero Point Configuration Process
HART DD
CAUTION
The touch screen of the 475 Field Communicator or AMS Trex Device Communicator should only be contacted by blunt
items. The use of a sharp instrument can cause damage to the touch screen interface.
DVC6200 Digital Valve Controller
February 2018
Instruction Manual Supplement
D104328X012

Other manuals for Fisher FIELDVUE DVC6200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fisher FIELDVUE DVC6200 and is the answer not in the manual?

Fisher FIELDVUE DVC6200 Specifications

General IconGeneral
BrandFisher
ModelFIELDVUE DVC6200
CategoryController
LanguageEnglish

Related product manuals