6. Specifications
6.1
Single-phase 200 V class series
Applicable motor rating (kW)
*1
0.4 0.75 1.5 2.2
Output Ratings
Rated capacity (kVA)
Three-phase, 200 to 240 V (with AVR function)
Rated current (A) *4
3.5 (2.5) 4.2 (4.2) 9.2 (7.5) 10.0 (10.0)
Overload capability
150% of rated output current for 1 min (for the rated current given in
parentheses)
Rated frequency (Hz)
Input Ratings
Phases, voltage,
Single-phase, 200 to 240 V, 50/60 Hz
frequency variations
Voltage: +10 to -10%, Frequency: +5 to -5%
Rated
current(A)
*6
(w/o
DCR)
5.4 9.7 16.4 24.0
supply capacity (kVA)
0.7 1.3 2.4 3.5
Braking
Braking starting frequency*9: 0.0 to 60.0 Hz,
Braking time: 0.0 to 30.0 s, Braking level: 0 to 100%
Applicable safety standards
UL61800-5-1, IEC 61800-5-1(under application)
IP20 (IEC 60529), UL open type (UL50)
*1 Fuji 4-pole standard motors
*2 Refers to the rated capacity assuming the rated output voltage as 220 V.
*3 Output voltages cannot exceed the power supply voltage.
*4 The load shall be reduced so that the continuous operating current is the rated current in parentheses or less if
the carrier frequency is set to 3 kHz or above or the ambient temperature exceeds 40°C.
*
5
Interphase
voltage
unbalance
(%)
=
Max.
voltage
(V)
-
Min.voltage
(V)
×
67
(Refer to
IEC
61800
- 3)
3
phase
average
voltage
(V)
If this value is 2 to 3%, use an optional AC reactor (ACR)
.
*6 Refers to the estimated value to apply when the power supply capacity is 500 kVA (inverter capacity x 10 when
the inverter capacity exceeds 50 kVA) and the inverter is connected to the %X = 5% power supply.
*8 Refers to the average braking torque to apply when the motor running alone decelerates from 60 Hz with the
AVR control being OFF. (It varies with the efficiency of the motor.)
*9 Available only for induction motor drive.