8-3. Current release control
The compressor frequency is controlled so that the outdoor unit input current does not exceeds cur-
rent limit value set according to the outdoor temperature.
The compressor frequency returns according to the operation mode, when the current becomes low-
er than the release value.
¢ Model: AOHG54KRTA
Operation mode Outdoor temp. (Ta) Trigger condition Release condition
Cooling
52°C ≤ Ta 4.5 A 4.0 A
50°C ≤ Ta < 52°C 5.5 A 5.0 A
46°C ≤ Ta < 50°C 6.5 A 6.0 A
42°C ≤ Ta < 46°C 7.5 A 7.0 A
2°C ≤ Ta < 42°C 8.5 A 8.0 A
Ta < 2°C 10.0 A 9.5 A
Heating
20°C ≤ Ta 6.5 A 6.0 A
16°C ≤ Ta < 20°C 7.0 A 6.5 A
12°C ≤ Ta < 16°C 8.0 A 7.5 A
2°C ≤ Ta < 12°C 8.5 A 8.0 A
Ta < 2°C 10.0 A 9.5 A
8-4. Indoor unit fan motor over temperature protection
When satisfy the following conditions, the protection works.
After the 90 seconds from the fan operation, detect less than 300 rpm for 10 seconds.
IPM trip protection works.
Current overload protection works.
When detecting the above condtion, recheck the condition after 6 minutes. When count the twice,
the protection works.
Protection contents
Reduce the static pressure 20 Pa. When it does not dissolve even the minimum static pressure
condition, work the following operation.
Fan motor error displayed when less than 300 rpm for 10 seconds is detected after the 90 sec-
onds from the fan operation.
Fan stop 40 seconds when IPM trip protection works.
Fan stop 50 seconds when corrent overload protection works.
8-5. Compressor temperature protection
When the compressor temperature sensor detects higher than the trigger condition below, the com-
pressor is stopped. When the compressor temperature sensor detects the release condition, the pro-
tection is released.
Trigger condition 108°C
Release condition
80°C
(3 minutes after compressor stop)
8-3. Current release control - (04-27) - 8. Various protections
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ABHG54KRTA and is the answer not in the manual?

Fujitsu ABHG54KRTA Specifications

General IconGeneral
BrandFujitsu
ModelABHG54KRTA
CategoryAir Conditioner
LanguageEnglish

Related product manuals