2-21. E: 73. Heat exchanger (Middle/Outlet) temperature
thermistor error (Outdoor unit)
Indicator
Wired remote
controller
Error code E: 73
Detective actuator
Heat exchanger liquid temperature
thermistor
• Heat exchanger liquid temperature thermistor short
or open detected
• Heat exchanger middle temperature thermistor
short or open detected
Heat exchanger middle
temperature thermistor
Forecast of cause
Connector failure
Thermistor failure
Main PCB failure
Check Point 1 : Check the connector connection and cable open
• Connector connection state check
• Cable open check
↓
Check Point 2 : Check the thermistor
• For the outdoor unit heat exchanger thermistor resistance value, refer to "Ther-
mistor resistance values" on page 03-57.
• If thermistor is either open or shorted, replace it and reset the power.
↓
Check point 3. Check voltage of main PCB
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor
(DC 5.0 V).
NOTE: For details of thermistor connector, refer to "Wiring diagrams" in Chapter 2.
TECHNICAL DATA AND PARTS LIST on page 02-13.
If the voltage does not appear, replace main PCB.
↓
End