EasyManuals Logo
Home>Fujitsu>Air Conditioner>ABHG54KRTA

Fujitsu ABHG54KRTA User Manual

Fujitsu ABHG54KRTA
154 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #60 background imageLoading...
Page #60 background image
2-21. E: 73. Heat exchanger (Middle/Outlet) temperature
thermistor error (Outdoor unit)
Indicator
Wired remote
controller
Error code E: 73
Detective actuator
Heat exchanger liquid temperature
thermistor
Heat exchanger liquid temperature thermistor short
or open detected
Heat exchanger middle temperature thermistor
short or open detected
Heat exchanger middle
temperature thermistor
Forecast of cause
Connector failure
Thermistor failure
Main PCB failure
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
Check Point 2 : Check the thermistor
For the outdoor unit heat exchanger thermistor resistance value, refer to "Ther-
mistor resistance values" on page 03-57.
If thermistor is either open or shorted, replace it and reset the power.
Check point 3. Check voltage of main PCB
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor
(DC 5.0 V).
NOTE: For details of thermistor connector, refer to "Wiring diagrams" in Chapter 2.
TECHNICAL DATA AND PARTS LIST on page 02-13.
If the voltage does not appear, replace main PCB.
End
2-21. E: 73. Heat exchanger (Middle/Outlet) temperature thermistor error (Outdoor
unit)
- (03-26) - 2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ABHG54KRTA and is the answer not in the manual?

Fujitsu ABHG54KRTA Specifications

General IconGeneral
BrandFujitsu
ModelABHG54KRTA
CategoryAir Conditioner
LanguageEnglish

Related product manuals