2-10. E: 58. Intake grille error (Indoor unit)
Indicator Indoor unit
Operation indicator 5 time flash
Timer indicator 8 time flash
Economy indicator Continuous flash
Error code E: 58
Detective actuator
Indoor unit main PCB
When the Micro switch is detected open while running
the compressor.
Micro switch
Forecast of cause
Micro switch failure
Shorted connector/wire
Main PCB failure
Check point 1. Check limit switch
Check operation of Micro switch. (any blocking by dust, etc.)
Remove Micro switch and check ON/OFF switching operation by using a meter.
-> If micro switch is detective, replace it.
Check point 2. Check connector (CN11)/wire
Check loose contact of CN11/shorted wire (pinched wire).
-> Replace micro switch if the wire is abnormal
Check point 3. Replace main PCB
If Check Point 1 and 2 do not improve the symptom, change main PCB.
End
2-10. E: 58. Intake grille error (Indoor unit) - (03-21) - 2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Other manuals for Fujitsu AOUG15LZAS1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOUG15LZAS1 and is the answer not in the manual?

Fujitsu AOUG15LZAS1 Specifications

General IconGeneral
BrandFujitsu
ModelAOUG15LZAS1
CategoryAir Conditioner
LanguageEnglish

Related product manuals