1-3. Dry operation
The rotation number of the compressor shall change according to the temperature, set temperature,
and room temperature variation which the room temperature sensor of the indoor unit has detected
as shown in the table below.
Zone is defined by set temperature and room temperature.
¢ Compact cassette type
Rotation number range of compressor
Unit: rps
Model: AOHG14KBTA2
Model name Outdoor temperature zone Operating rotation number
AUXG07KVLA
AUXG09KVLA
AUXG12KVLA
X zone 50
J zone 50
Y zone 0
AUXG14KVLA
X zone 44
J zone 44
Y zone 0
Model: AOHG18KBTA2
Model name Outdoor temperature zone Operating rotation number
AUXG07KVLA
AUXG09KVLA
AUXG12KVLA
X zone 50
J zone 50
Y zone 0
AUXG14KVLA
X zone 42
J zone 42
Y zone 0
Compressor control based on room temperature
Ts+0.5°C
Ts -1.5°C
Ts-0.5°C
Ts+1.5°C
X zone
J zone
Y zone
Room temperature drops
Room temperature rises
Ts: Set temperature
1-3. Dry operation - (04-15) - 1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS

Table of Contents

Other manuals for Fujitsu ARXG12KLLAP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARXG12KLLAP and is the answer not in the manual?

Fujitsu ARXG12KLLAP Specifications

General IconGeneral
BrandFujitsu
ModelARXG12KLLAP
CategoryAir Conditioner
LanguageEnglish

Related product manuals