4-2. Power supply cable wiring
¢
Power supply cable specifications
Indoor unit
Electrical requirement
Power supply cable
Minimum conductor size
mm
2
1.5
Transmission cable
Bus wire
Minimum conductor size
mm
2
0.33
Maximum length m 500*
NOTES:
*: This length shall be the total extended length in the system of the group. (Total length of
bus wire and remote controller cable.)
Use confirmed cable with type 245 IEC 57. (Power supply cable or transmission cable)
Perform all electrical work according to the standard.
Install a circuit breakers, which have the terminal spacing of more than 3 mm, in a place of
near the indoor unit and outdoor unit.
Wiring size must comply with the applicable local and national code.
Outdoor unit
Breaker and wiring specifications
Breaker capacity A 30
Power supply cable Minimum conductor size
mm
2
6
NOTES:
Use confirmed cable with type 245 IEC 57.
Perform all electrical work according to the standard.
Install a circuit breaker with a contact gap of at least 3 mm in all poles nearby the units.
(Both indoor units and outdoor units)
Install the circuit breaker nearby the units.
Wiring size must comply with the applicable local and national code.
- 116 -
4-2. Power supply cable wiring 4. Wiring design
SYSTEM
DESIGN
SYSTEM
DESIGN

Table of Contents

Other manuals for Fujitsu ARXG24KMLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARXG24KMLA and is the answer not in the manual?

Fujitsu ARXG24KMLA Specifications

General IconGeneral
BrandFujitsu
ModelARXG24KMLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals