2-3. Duct type
Model name ARXG22KMLA ARXG24KMLA
Power supply 3N 400 V ~50 Hz
Power supply intake Outdoor unit
Available voltage range 342—457 V
Fan
Airflow rate
Cooling
HIGH
m
3
/h
1,100
MED 910
LOW 750
QUIET 580
Heating
HIGH 1,100
MED 910
LOW 750
QUIET 580
Type × Q'ty Sirocco fan × 2
Motor output W 106
Recommended static pressure Pa 30 to 150
Sound pressure level*
1
Cooling
HIGH
dB (A)
31
MED 29
LOW 27
QUIET 25
Heating
HIGH 31
MED 29
LOW 27
QUIET 25
Heat exchanger type
Dimensions (H × W × D) mm 294 × 1,000 × 39.9
Fin pitch mm 1.40
Rows × Stages 3 × 14
Pipe type Copper
Fin type Aluminum
Enclosure
Material Steel sheet
Color —
Dimensions
(H × W × D)
Net
mm
270 × 1,135 × 700
Gross 300 × 1,320 × 790
Weight
Net
kg
35
Gross 43
Connection
pipe
Size
Liquid
mm (in)
Ø 6.35 (1/4)
Gas Ø 12.70 (1/2)
Method Flare
Operation range
Cooling
°C 18 to 32
%RH 80 or less
Heating °C 16 to 30
Drain port
Material Steel
Size mm Ø 35.7 (I.D.), Ø 38.1 (O.D.)
Remote controller type (option)
Wired remote controller, Wireless remote controller, Mobile app*
2
(FGLair
™
)
NOTES:
• Values mentioned in the table are based on the following conditions:
– Static pressure: 35 Pa
• The protective function might work when using it outside the operation range.
• *1: Sound pressure level:
– These are the measured values in the manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• *2: Available on Google Play
™
store or on App Store
®
. Optional WLAN adapter is also required. For details, refer to the setting manual.
- 5 -
2-3. Duct type 2. Specifications
INDOOR UNITS
SIMUL. MULTI-SPLIT
INDOOR UNITS
SIMUL. MULTI-SPLIT