EasyManuals Logo
Home>Fujitsu>Air Conditioner>ARXG24KMLA

Fujitsu ARXG24KMLA User Manual

Fujitsu ARXG24KMLA
228 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #142 background imageLoading...
Page #142 background image
Indoor unit fan operation status
Function setting External output Output signal Command
60—10 CN47
Low → High Fan run
High → Low Fan stop
Output signal Condition
On
The indoor unit fan is operating.
Low → High
Off
The fan is stopped or during cold air prevention.
During thermostat off when in dry mode operation.
High → Low
Fan run
Fan stop
High
Low
CN47
Indoor unit
External heater output
Function setting External output Output signal Command
60—11 CN47
Low → High Heater on
High → Low Heater off
Output signal Condition
Low → High
Heater turns on as shown in diagram of heating temperature
Off → On
High → Low
Heater turns off as shown in diagram of heating temperature
Other than Heating mode
Error occurred
On → Off
Forced thermo off
Fan stop protection
Specifications of the signal output performance are as shown as follows:
Example:When set temperature (Ts) is set at 22 °C;
And room temperature (Tr) increase above 12 °C, signal output is on.
And Tr increase above 21 °C, signal output is off.
And Tr decrease below 19 °C, signal output is on.
And Tr decrease below 10 °C, signal output is off.
Off
Off
On
Tr-Ts
Tr-Ts=-1 °C
Tr-Ts=-10 °C
Tr-Ts=-3 °C
Tr-Ts=-12 °C
The output also turns off in defrost operation.
- 134 -
6-1. Indoor unit 6. External input and output
SYSTEM
DESIGN
SYSTEM
DESIGN

Table of Contents

Other manuals for Fujitsu ARXG24KMLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARXG24KMLA and is the answer not in the manual?

Fujitsu ARXG24KMLA Specifications

General IconGeneral
BrandFujitsu
ModelARXG24KMLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals