When function setting is "Operation/Stop" mode 2
Function setting External input Input signal Command
46—03 Terminal
Off → On Operation
On → Off Stop (R.C. disabled)
On
Input
Off
Operation
Indoor unit
Stop
(R.C. disabled)
Remote controller
On OnOff
NOTE: When "Operation/Stop" mode 2 function is used with forming a remote controller group,
connect the same equipment to each indoor unit within the group.
¢
Control output function
Function setting External output Output signal Command
60—00 CN47
Low → High Operation
High → Low Stop
The output is low when the unit is stopped.
Operation
Stop
High
Low
CN47
Indoor unit
¢
Error status
Function setting External output Output signal Command
60—09 CN47
Low → High Error
High → Low Normal
The output is ON when an error is generated for the indoor unit.
Error
Normal
High
Low
CN47
Indoor unit
- 54 -
8-4. Details of function
8. External input and output
DUCT TYPE
ARXG24-45KMLA
DUCT TYPE
ARXG24-45KMLA

Table of Contents

Other manuals for Fujitsu ARXG36KMLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARXG36KMLA and is the answer not in the manual?

Fujitsu ARXG36KMLA Specifications

General IconGeneral
BrandFujitsu
ModelARXG36KMLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals