1. Specifications
Type Inverter heat pump
Model name ARXG24KMLA ARXG30KMLA ARXG36KMLA ARXG45KMLA
Power supply 230 V ~ 50 Hz
Power supply intake Outdoor unit
Available voltage range 198—264 V
Capacity
Cooling
Rated
kW 6.8 8.5 9.5 12.1
Btu/h 23,200 29,000 32,400 41,300
Min.—Max.
kW 0.9—7.4 2.8—9.6 2.8—10.6 4.0—12.6
Btu/h 3,100—25,200 9,600—32,700 9,600—36,100 13,600—43,000
Heating
Rated
kW 7.5 10.0 10.8 13.5
Btu/h 25,600 34,100 36,900 46,100
Min.—Max.
kW 0.9—8.6 2.7—10.8 2.7—12.5 4.2—15.0
Btu/h 3,100—29,300 9,200—36,800 9,200—42,600 14,300—51,200
Input power
Cooling
Rated
kW
2.19 2.78 3.13 4.84
Max. 2.69 3.83 4.29 5.03
Heating
Rated 2.00 2.77 3.03 4.18
Max. 2.65 4.37 4.66 4.79
Current
Cooling
Rated A
9.7 12.3 13.8 21.3
Heating 8.8 12.3 13.4 18.3
Power factor
Cooling
%
98.5 98.1 98.3 99.0
Heating 98.7 97.7 98.2 99.1
EER Cooling
kW/kW
3.11 3.06 3.04 2.50
COP Heating 3.75 3.61 3.56 3.23
Moisture removal L/h (pints/h) 2.5 (4.4) 3.0 (5.3) 4.0 (7.0)
Maximum operating current *1
Cooling
A
12.6 22.5 28.1
Heating 12.6 22.5 28.1
Fan
Airflow rate
Cooling
HIGH
m
3
/h
1,100 1,900 2,100
MED 910 1,620 1,750
LOW 750 1,270 1,350
QUIET 580 980 1,070
Heating
HIGH 1,100 2,100
MED 910 1,620 1,750
LOW 750 1,270 1,350
QUIET 580 980 1,070
Type × Q'ty Sirocco × 2
Motor output W 106 197
Static pressure range Pa 30 to 150
Sound pressure level *2
Cooling
HIGH
dB (A)
31 39 42
MED 29 35 38
LOW 27 30 32
QUIET 25 26 28
Heating
HIGH 31 42
MED 29 35 38
LOW 27 30 32
QUIET 25 26 28
Sound power level
Cooling
HIGH dB (A)
60 65 68
Heating 62 69 70
Heat exchanger type
Dimensions (H × W × D)
mm
294 × 1,000 × 39.9 294 × 1,000 × 53.2
Fin pitch 1.40
Rows × Stages 3 × 14 4 × 14
Pipe type Copper
Fin type Aluminum
Enclosure
Material Steel sheet
Color —
Dimensions
(H × W × D)
Net
mm
270 × 1,135 × 700
Gross 300 × 1,320 × 790
Weight
Net
kg
35 38 39
Gross 43 45 47
Connection pipe
Size
Liquid
mm (in)
Ø 6.35 (Ø 1/4) Ø 9.52 (Ø 3/8)
Gas Ø 12.70 (Ø 1/2) Ø 15.88 (Ø 5/8)
Method Flare
Drain port
Material Steel
Size mm Ø 35.7 (I.D.), Ø 38.1 (O.D.)
Operation range
Cooling
°C 18 to 32
%RH 80 or less
Heating °C 16 to 30
Remote control (Option)
Wired remote controller, Wireless remote controller, Mobile app*3 (FGLair
™
)
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Standard static pressure; 24 type: 35 Pa, 30 and 36 types: 47 Pa, 45 type: 60 Pa
– Pipe length: 5.0 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Maximum operating current is the total current of the indoor unit and the outdoor unit.
• *2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• *3: Available on Google Play
™
store or on App Store
®
. Optional WLAN adapter is also required. For details, refer to the setting manual.
• This data is based on EN 14511 standard.
- 2 -
1. Specifications
DUCT TYPE
ARXG24-45KMLA
DUCT TYPE
ARXG24-45KMLA